31
Bentone
172 625 09
8.6
Fan
1.
Disconnect the main power and shut off the fuel supply.
2.
Detach the electrical panel (Y).
3.
Loosen the motor electrical connection and screws (X) enough to turn
and lift out the motor.
4.
Check the fan wheel attachment and any skew, replace if damaged.
5.
Clean or replace the fan wheel.
6.
Refi t the parts.
7.
Switch on the main power and open the fuel supply.
8.
Start burner and check/adjust combustion.
!
Before obtaining access to electrical and fuel line components
all supply circuits must be disconnected.
!
When servicing/replacing components that aff ect combustion,
fl ue gas analysis and soot test must be carried out following
installation.