16
Bentone
172 515 06-2 2022-11-28
!
Check for leaks in the gas line.
5. Mounting
The burner is mounted on the boiler according to the hole pattern on the
fixing flange.
1.
Remove the gas valve from the burner.
2.
Remove fan housing by loosening nut (A), swing out fan housing.
Disconnect ionisation and ignition cables from the electrodes.
Remove nut (B) on hinged flange and lift fan housing off.
3.
Install the fixing flange and the supplied gasket on the boiler. If
new mounting holes need to be drilled, use the fixing flange as a
template and fasten with M8-M12 screws.
4.
Check that the electrodes are correctly set, see chapter Gas
nozzle.
5.
Mount the fan housing on the fixing flange and fasten with nut
(B).
6.
Connect the ionisation and ignition cables.
7.
Fit the gas valve.
8.
Connect the gas with the ball valve provided. Ensure that the pre-
screwing, ball valve and tubings are done in such a way that the
burner and boiler hatch can be easily used for servicing.
9.
Connect the supply cable, operating and safety circuits.
B
A
Содержание BG 300-2
Страница 26: ...26 Bentone 7 7 1 Pressure taps 1 2 3 4 5 1 8 screwed sealing plug 7 7 2 Electrical connection S 20 S 50...
Страница 42: ......
Страница 43: ......
Страница 44: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com...