An outlet valve situated at the opposite end of the
tank to the sludge valve.
•
A fi ller pipe connection situated at the opposite end
to the outlet valve.
The size of the storage tank must take account of the
estimated consumption and any quantity price breaks off ered
by the oil supplier.
It is preferable to install the tank outside, however, if this
is not practicable and the tank has to be installed indoors
advice must be sought about its siting, especially so far as fi re
regulations are concerned.
If a separate fi re resistant chamber cannot be provided for
indoor installations, a catchment pit with a capacity 10%
greater than that of the storage tank must be provided
Storage tanks can if necessary be sited on a roof, but this is
subject to special regulations as well as local authority
approval and compliance with fi re regulations, reference to
BS 5410 part 2 1978 & part 1 1997 is strongly suggested.
It is advisable to leave the tank unpainted on the inside, but
to paint the outside with a proprietary grade of anti-corrosive
paint.
Warning
A galvanised or open topped tank is strictly not allowed.
Warning
All oil storage tanks require a bund
The Control of Pollution Regulation (Oil Storage) 2001 should
be consulted prior to installation.
1.9.3 Single pipe system (gravity feed)
For installations where the oil tank is 200mm or more above
the level of the fuel pump the principle of gravity feed may be
used.
The draw off point for the supply to the burner must not be
positioned any lower than 100mm above the bottom of the
tank.
Where a return valve is fi tted this must be tamper proof to
prevent inadvertent operation.
C
aution
If the valve is closed when the pump is running the oil
pressure can be increased suffi
ciently so as to cause damage
to the seals within the pump.
The return oil should preferably be discharged through an
elbow onto a tank plate situated within the tank, this should
be positioned so as not to introduce air or air bubbles into the
draw off pipe.
1.9.4 Two pipe system
This is used where the oil storage tank is lower than the pump.
Access for the fuel feed to the burner should be via a suitable
tapping made in the top of the tank, and the fuel feed pipe
should extend to not less than 100mm above the bottom of
the tank.
A none return valve with a metal to metal seat should be
fi tted, especially if the return pipe work is terminated at a
level above the draw off tube. The non- return valve must be
removable for service and maintenance purposes, and the
return pipe from the pump must therefore be extended down
into the tank to the same level as the suction pipe.
The presence of a tamper proof isolating valve fi tted within
the return pipe is only required if there is a risk that oil will
siphon out of the tank if the return pipe is disconnected at the
pump during maintenance or servicing and if the none return
valve has been omitted.
Caution
The Deareator must be fi tted the burner side of the inlet fuel
fi lter
Maximum lift should not exceed 3.5 metres, and the vacuum
should not exceed 0.4 bar.
Each heater must have a separate fuel supply.
Note
It is strongly recommended that the separate manual
concerning the operational details of the burner supplied with
the heater as part of the information package is studied prior
to installation.
1.9.5 Pressurised ring main system
This system is used to supply a number of units from a
common storage tank.
A booster pump is used to provide the pressure to push the oil
around the ring main and back to the tank.
Pressure reducing valves should be fi tted on the delivery pipe
to each heater to ensure that the pressure at the burner pump
is less than
6 psi.
Содержание OUH 2 100
Страница 20: ...Wiring Diagram 33 65 245 Models OUHA OUHC40 ON OFF Riello Oil Fried Burner...
Страница 21: ...Wiring Diagram 33 65 246 Models OUHA 60 70 ON OFF Riello Oil Fried Burner...
Страница 22: ...Wiring Diagram 73 65 010 Models OUHA 90 100 ON OFF Riello Oil Fried Burner...
Страница 23: ...Wiring Diagram 33 65 247 Models OUHC 60 100 ON OFF Riello Oil Fried Burner...
Страница 24: ...Wiring Diagram 33 65 248 Models OUHA OUHC 40 HI LOW Riello Oil Fried Burner...
Страница 25: ...Wiring Diagram 33 65 249 Models OUHA 60 70 HI LOW Riello Oil Fried Burner...
Страница 26: ...Wiring Diagram 73 65 011 Models OUHA 90 100 HI LOW Riello Oil Fried Burner...
Страница 27: ...Wiring Diagram 33 65 250 Models OUHC 60 100 HI LOW Riello Oil Fried Burner...
Страница 28: ...Remote Connections 33 65 132 ON OFF HI LOW Less Controls Remote Connections 33 65 228 ON OFF to SmartCom SC3 SZ...
Страница 29: ...Remote Connections 33 65 229 HI LOW to SmartCom SC3 MZ Remote Connections 33 65 131 ON OFF HI LOW to CP4...
Страница 35: ...Turbulator positions in models 40 70 8 off Turbulator positions in models 90 100 12 off...
Страница 43: ...Notes...