1403BSHH_AMEN,page 9/29
D
C
m
in
5
0m
m
A PVC tube with collar of dia 32 is provided to drain the
condensate from the heat exchanger. The condensate
trap is optional.
Ensure that dimensioning of condensate drain can
handle condense rates as indicated below.
Condense drain rates of flow
BSHH
055 083 102
Nat.
gas
l/h 22 33 41
Propane
l/h 13 19 24
REMARK : Fill condensate trap with clean water before
commissioning the unit.
Figure 6
D = minimum 130mm
C = D + minimum 50mm (= min. 180mm)
Condensate trap (option nr OP928)