background image

BENNING IT 130 

short instructions 

 

- 5 - 

 

 Warnings related to safety – measurements 

 

Insulation resistance 

 

Insulation resistance measurement should only be performed on de-energized objects! 

 

Do not touch the test object during the measurement or before it is fully discharged! Risk of 

electric shock! 

 

When  an  insulation  resistance  measurement  has  been  performed  on  a  capacitive  object, 

automatic discharge may not be done immediately! The warning message 

 and the actual 

voltage (Udisch) are displayed during discharge until voltage drops below 30 V. 

 

Do not connect test terminals to external voltage higher than 600 V (AC or DC) in order not to 

damage the test instrument! 

 

Low-impedance resistance/continuity test 

 

Low-impedance resistance measurements/ continuity tests should  only  be performed on de-

energized objects! 

 

Parallel loops may influence on test results. 

 

Testing PE terminal 

 

If the phase voltage is detected at the protective conductor connection PE, immediately stop all 

measurements and ensure that the fault of the installation will be eliminated. 

 

 

 

Warnings related to safety – batteries/ storage batteries and fuses 

 

 

Disconnect all test cables / accessories from the tester and from the installation and switch the 

tester off before opening the cover of the battery / fuse compartment. Dangerous voltages 

may be applied to the interior of the tester! 

 

Please make sure that the storage batteries are inserted correctly, because otherwise the tester 

is not ready for operation and the storage batteries will discharge. 

 

Do not recharge alkaline battery cells! 

 

The storage batteries must be charged only by means of the charger included in the scope of 

delivery! 

 

 

 

Warnings related to safety  – "Commander" probe tip (included in delivery) 

 

– "Commander" test plug for shock-proof socket (optional) 

 

Measuring category of commanders: 

"Commander" probe tip (cap off, 18 mm tip) 

CAT II 1000 V to earth 

"Commander" probe tip (cap on, 4 mm tip) 

CAT II 1000 V / CAT III 600 V / CAT IV 300 V to earth 

"Commander" test plug for shock-proof socket  CAT II 300 V to earth 

 

 

Measuring category of commanders can be lower than protection category of the instrument. 

 

If dangerous voltage is detected on the tested PE terminal, immediately stop all measurements, 

find and remove the fault! 

 

Disconnect the "Commander" from the tester and from the installation and switch the 

"Commander" off before opening the cover of the battery compartment. Dangerous voltages 

might occur inside the "Commander"! 

 

 

Содержание 044103

Страница 1: ...Installation Tester BENNING IT 130 Short instructions GB Detailed instruction manual on enclosed CD Rom...

Страница 2: ...o KG M nsterstra e 135 137 D 46397 Bocholt Phone 49 0 2871 93 0 Fax 49 0 2871 93 429 www benning de duspol benning de 05 2020 BENNING This document must not be reproduced or used in any other form wit...

Страница 3: ...and fuses 11 1 10 Calibration and Service 12 1 11 Optional accessories 13 2 Measurements 14 2 1 Null balance compensation of the test cables 14 2 2 TRMS voltage V AC DC frequency and phase sequence r...

Страница 4: ...inspection and repair Do not use the instrument in AC supply systems with voltages higher than 550 V AC Service repairs or adjustment of instruments and accessories is only allowed to be carried out b...

Страница 5: ...isconnect all test cables accessories from the tester and from the installation and switch the tester off before opening the cover of the battery fuse compartment Dangerous voltages may be applied to...

Страница 6: ...ntrast 8 ON OFF Switches the instrument power on or off The instrument automatically turns off 15 minutes after the last key was pressed 9 HELP CAL Help function with connection diagrams press for app...

Страница 7: ...rying case item no 10008291 1 x Commander test probe switchable by means of TEST key item no 044155 1 x test cable with shock proof plug item no 10008295 1 x universal three wire test cable black blue...

Страница 8: ...N Battery indication Battery capacity indication Low battery The storage battery charge condition is too low to ensure correct measuring results Recharge the storage batteries or replace the batteries...

Страница 9: ...urrent clamp can be increased Measured signal is out of range clipped Results are impaired Simple error in the IT network Fuse F1 F2 or F3 is defective If one of the fuses F2 or F3 has blown the devic...

Страница 10: ...T network RCD TESTING according to EN 61008 EN 61009 IEC 60364 4 41 BS 7671 AS NZS 3017 SET ISC FACTOR setting 0 20 3 00 SELECT COMMANDER ON OFF INITIAL SETTINGS CLAMP SETTINGS BENNING CC 1 044037 BEN...

Страница 11: ...e batteries will be recharged automatically as soon as the charger is connected to the charging socket An integrated protective circuit controls the charging process Power supply socket polarity Note...

Страница 12: ...rantees compliance with the technical and accuracy specifications stated in the operating manual for the first 12 months after the delivery date To maintain accuracy of the measuring results the devic...

Страница 13: ...terior lighting Commander test plug For shock proof socket switchable with TEST and MEM keys with PASS FAIL indication by means of green red LED PE contact electrode for detecting a phase voltage at t...

Страница 14: ...t the test cables Shorted test leads 3 Press the key 4 Press the key CAL HELP After performing test leads compensation first measured value and then 0 00 is displayed Successful compensation is displa...

Страница 15: ...se adapter optional in a three phase system 3 The measuring result can be stored by means of the MEM key Uln Voltage between phase L and neutral conductors N Ulpe Voltage between phase L and protectiv...

Страница 16: ...500 V 1000 V Minimum limiting value without 0 01 M 200 M 3 Connection diagrams Connection of 3 wire test lead and Commander probe tip 4 Press and hold the key until result is stabilized Double click...

Страница 17: ...NUITY function 3 Connection diagrams Connection of the three wire test cable and of the optional measuring line BENNING TA 5 044039 Connection of 3 wire test lead and Commander probe tip 4 a R LOW low...

Страница 18: ...actor for test current x I N 1 2 5 x I N Limiting value for contact voltage 25 V 50 V 3 Connection diagrams Connecting the Commander test plug optional TN 044149 and the 3 wire test lead 4 Press the k...

Страница 19: ...CD Fuse type gL gG gG B C K D Nominal current of the fuse Tripping time of the fuse 3 Connection diagrams Connecting the Commander test plug 044149 and the 3 wire test lead 4 Press the key 5 The measu...

Страница 20: ...tion of the optional Commander test plug 044149 and of the three wire test cable Voltage drop Connection of the optional Commander test plug 044149 and of the three wire test cable 4 Press the key 5 T...

Страница 21: ...nce Maximum limiting value without 1 5 k 3 Connection diagrams Connection of the optional earthing set 044113 4 Press the key 5 The measuring result can be stored by means of the MEM key R Earth resis...

Страница 22: ...unction I Note Please set the current clamp adapter used under SETTINGS 2 Connection diagrams Connection of the optional current clamp adapter BENNING CC 1 044037 BENNING CC 3 044038 4 Press the key 5...

Страница 23: ...Set function 2 Set limit LUX Minimum illumination OFF 0 1 lux 20 klux 3 Connection diagrams Positioning of the luminous intensity sensor BENNING luxmeter type B 044111 4 Press the key 5 The measuring...

Страница 24: ...t RISO ISFL Single fault leakage current only in IT networks Maximum limiting value without 3 0 mA 20 0 mA 3 Connection diagrams Connection of the three wire test cable 4 Press the key 5 The measuring...

Отзывы: