32
tst3
Enables or disables the BAR input TEST.
Activation of the TEST function is only possible using items SC.RF and RF/RF.SUN, consult
the specific instructions.
On: Check enabled. If the check has a negative outcome, no manoeuvre is commanded.
See Fig.15 - “BAR TEST”. (AUX=4)
Off: Test disabled.
(OFF)
phcl
Selection of the PHOT CL input operating mode.
On: PHOT CL input enabled only in closure.
In closure: opening of the contact causes stoppage of the motor and instantaneous inver-
sion of the running direction (opens).
Off: Active PHOT CL input both in closure and opening.
In opening: opening of the contact caused by stoppage of the motor, when the photocell
is free, motor opening restarts.
In closure: opening of the contact causes stoppage of the motor, when the photocell is free,
the motor running direction inverts (opens).
(OFF)
1mot
Selection of the motors 1 or 2 operating mode.
On: Use for a single motor, connected to output M1
Off: Use for two motors.
(OFF)
minv
Motors start order:
On: motor 2 starts first in opening.
Off: motor 1 starts first in opening.
(OFF)
aopf
Enables or disables the “Forced opening function without mains) function (can only be
enabled with the emergency batteries connected and working).
On: Function enabled. In the event of a power cut, before the emergency battery goes
completely flat, the control panel forces an opening manoeuvre.
The automation remains open until the mains power supply is restored.
Off: Function not enabled.
(OFF)
ham
Enables or disables inversion strike.
On: Function enabled. Before each opening movement, the control panel commands a 2s
movement in the opposite direction to facilitate release of the solenoid valve.
Off: Function disabled.
(OFF)
blco
Enables or disables the block in opening function.
On: Block function enabled.
Do not use on SAM gearmotors
.
Off: Block function disabled.
(OFF)
blcc
Enables or disables the block in closure function.
On: block function enabled.
Do not use on SAM gearmotors
.
Off: Block function disabled.
(OFF)
mloc
Selects the type of electric lock used.
On: Magnetic electric lock, normally powered according to the Vloc setting. Output en-
abled with gate closed.
Off: Latch electric lock, normally not powered.
Before each opening movement, it is supplied according to the Vloc setting for the time set
by the TLOC parameter.
(OFF)
cvar
Enables or disables the cloned ARC transmitters.
On: The AK series transmitters closed from an ARC transmitter already stored are enabled.
Off: The cloned transmitters are not enabled.
(ON)
rem
Enables or disables remote learning of the radio transmitters, as indicated in the
“Transmitters remote learning” paragraph.
On: Remote learning enabled.
Off: Remote learning disabled.
(ON)
esa
Enables or disables the “ESA” energy saving functionality.
On: The control unit, once the manoeuvre has terminated and enabling time is up of the
service light, removes the power supply to the accessories output, setting in stand-by
status.
The power supply of the accessories however remains enabled, only for the necessary time,
if the AUX1/AUX2 parameters need it.
Off: Energy saving disabled. To use if you want to have the accessories power supply
always enabled, for example if using 24 Vdc, or other devices that need to be always
powered.
(ON)