31
EN
* ATTENTION: FURTHER SETTING OF THESE PARAMETERS CAN BE DANGEROUS.
COMPLY WITH LEGISLATION IN FORCE!
With the motors without a limit switch and/or encoder, adjust the sensitivity of the sensor that causes stoppage during the
slowdown phase.
** 1: minimum force/torque - 99: maximum force/torque.
The control panel avails of two anti-crushing devices: the amperometric sensor (adjusted by parameters PMO1/2-PMC1/2-PSO1/2-
PSC1/2) and the encoder (adjusted by the SEAV and SEAR parameters).
Using the Autoset procedure, the sensitivity of the amperometric sensor is adjusted by default, while the encoder (with default setting)
only activates if the gate stops completely following impact.
You are advised to only use a system at a time, giving preference to the amperometric sensor, whose response time is less.
LOGIC (
LOG
)
MENU
FUNCTION
ON-OFF-
(Default)
MEMO
TCA
Enables and disables automatic closure.
On: automatic closure enabled.
Off = automatic closure disabled
(ON)
IbL
Enables or disables the shared function.
On: shared function enabled. The S.S. or transmitter impulse has no effect during the
opening phase.
Off: apartment complex function disabled.
(OFF)
ibca
Enables or disables the condominium function during TCA counting.
On: apartment complex function enabled. The PP or transmitter pulse has no effect during
TCA counting.
Off: apartment complex function disabled.
(OFF)
PP
Select the operating mode of the ”P.P. button” and the transmitter.
On: “Operation”; OPEN> CLOSE > OPEN>
Off: “Operation”; OPEN>STOP>CLOSE>STOP>
(OFF)
pre
Enables or disables pre-flashing.
On: Pre-flashing enabled. The flashing light activates 3s before the motor starts.
Off: Pre-flashing disabled.
(OFF)
SCL
Enables and disables rapid closure.
On: rapid closure enabled. With the gate open or in the opening phase, intervention of the
photocell causes automatic closure 3 s after complete opening. Active only with TCA:ON
Off = rapid closure disabled
(OFF)
htr
Person present function enabled or disabled.
On: Person Present Operation
The APRE/CHIUDE button must be kept pressed throughout the manoeuvre. Opening the
STOP input stops the motor. All the safety inputs are disabled.
Off: Automatic/semi-automatic operation.
(OFF)
LTCA
Selection of the flashing light operating mode during the TCA time
On: Flashing indicator light on during TCA
Off: Flashing indicator light off during TCA
(OFF)
MBLK
Sets the BLINK flashing output operating mode.
On: The output provides intermittent voltage during the manoeuvre phase (2 flashes per
second).
Off: The output provides continuous voltage during the manoeuvre phase.
(OFF)
TST1
Enables or disables the photocells check on the PHOT Op input, enabled both in closure
and in opening.
On: Check enabled. If the check has a negative outcome, no manoeuvre is commanded.
See Fig.16/17 - “PHOTO TEST”. (AUX=4)
Off: Check the photocells on each disabled manoeuvre. This setting requires maintenance
of photocells every 6 months.
(OFF)
tst2
Enables or disables the photocells check on the PHOT Cl input, enabled both in closure
and in opening.
On: Check enabled. If the check has a negative outcome, no manoeuvre is commanded.
See Fig.16/17 - “PHOTO TEST”. (AUX=4)
Off: Check the photocells on each disabled manoeuvre. This setting requires maintenance
of photocells every 6 months.
(OFF)
Содержание SAM
Страница 2: ......
Страница 6: ...6 10 11 OK NO OK NO OK NO L C C M C R R G ...
Страница 92: ...AUTOMATISMI BENINCÀ SpA Via Capitello 45 36066 Sandrigo VI Tel 0444 751030 r a Fax 0444 759728 ...