33
EN
AUTOSET (
AUTO
)
The automatic system stroke is self learned. See section “STROKE SELF-LEARNING”
PASSWORD (
CODE
)
It allows to type in an access protection code to the programming of the control unit.
A four-character alphanumeric code can be typed in by using the numbers from 0 to 9 and the letters A-B-C-D-E-F.
The default value is 0000 (four zeros) and shows the absence of a protection code.
While typing in the code, this operation can be cancelled at any moment by pressing keys + and – simultaneously. Once the password
is typed in, it is possible to act on the control unit by entering and exiting the programming mode for around 10 minutes in order to
allow adjustments and tests on functions.
By replacing the 0000 code with any other code, the protection of the control unit is enabled, thus preventing the access to any other
menu. If a protection code is to be typed in, proceed as follows:
- select the Code menu and press OK.
- the code 0000 is shown, also in the case a protection code has been previously typed in.
- the value of the flashing character can be changed with keys + and -.
- press OK to confirm the flashing character, then confirm the following one.
- after typing in the 4 characters, a confirmation message “CONF” appears.
- after a few seconds, the code 0000 appears again
- the previously stored protection code must be reconfirmed in order to avoid any accidental typing in.
If the code corresponds to the previous one, a confirmation message “OK” appears.
The control unit automatically exits the programming phase. To gain access to the Menus again, the stored protection code must be
typed in.
IMPORTANT: TAKE NOTE of the protection code and KEEP IT IN A SAFE PLACE for future maintenance operations.
To remove the code from a protected control unit, enter the programming mode with the password and reset the
code to the 0000 default value.
IF YOU LOOSE THE CODE, PLEASE CONTACT THE AUTHORISED SERVICE CENTER FOR THE TOTAL RESET OF
THE CONTROL UNIT.
12.8) MOTOR TYPE SELECTION (
MOT1
)
Allows to select the setting of the control unit according to the type of motor to be used.
Normally the right value is set by default and it does not need to be changed by the end user.
Only in case of control unit replacement is necessary to set the right value. Every number correspond to a defined type of motor, as
shown in the list below.
0: YAK25
1: BULL 15 OMI 230Vac
2: BULL 15 OMAI 115Vac
3: NOT USED
For convenience the screen shows always the message MOT followed by the number of the motor currently set
(eg. MOT.1,MOT.2)
TAB. 1
BULL 15 OMI
Kg
Max. FSTO/ FSTC
Min. TBR
Min. TSMO/TSMC
PMO/PMC
V (m/1’)
1500
120
4
45
99/99
24
1000
100
3
35
99/99
20
600
85
2
30
99/99
17,5
According to the motor type and weight of the leaf, set the value of the speed during the opening and closing phase (FSTO/FSTC), the
maximum value of the braking TBR and the slowdown space values TSMO/TSMC.
The PMO/PMC parameters must be at 99.
BRAKE RESISTOR MUST be connected.
Exceed the recommended values may cause damage and malfunctioning. The manufacturer does not assume liability resulting from
improper setting of values FSTO/FSTC/TBR/TSMO/TSMC.
THE REPORTED VALUES ARE APPROXIMATE AND REFERED TO A STANDARD INSTALLATION, IN ANY CASE THE INSTALLATION
MUST BE DONE ACCORDING TO THE REGULATIONS IN FORCE (MACHINERY DIRECTIVE 2006/42/CE AND THE EUROPEAN
STANDARDS EN 13241-1, EN 12453, EN 12445).