33

EN

AUTOSET (

AUTO

)

The automatic system stroke is self learned. See section “STROKE SELF-LEARNING”

PASSWORD (

CODE

)

It allows to type in an access protection code to the programming of the control unit.
A four-character alphanumeric code can be typed in by using the numbers from 0 to 9 and the letters A-B-C-D-E-F.
The default value is 0000 (four zeros) and shows the absence of a protection code.
While typing in the code, this operation can be cancelled at any moment by pressing keys + and – simultaneously. Once the password 
is typed in, it is possible to act on the control unit by entering and exiting the programming mode for around 10 minutes in order to 
allow adjustments and tests on functions.
By replacing the 0000 code with any other code, the protection of the control unit is enabled, thus preventing the access to any other 
menu. If a protection code is to be typed in, proceed as follows:
- select the Code menu and press OK.
- the code 0000 is shown, also in the case a protection code has been previously typed in.
- the value of the flashing character can be changed with keys + and -.
- press OK to confirm the flashing character, then confirm the following one. 
- after typing in the 4 characters, a confirmation message “CONF” appears.
- after a few seconds, the code 0000 appears again
- the previously stored protection code must be reconfirmed in order to avoid any accidental typing in.
If the code corresponds to the previous one, a confirmation message “OK” appears.
The control unit automatically exits the programming phase. To gain access to the Menus again, the stored protection code must be 
typed in.

IMPORTANT: TAKE NOTE of the protection code and KEEP IT IN A SAFE PLACE for future maintenance operations. 
To remove the code from a protected control unit, enter the programming mode with the password and reset the 
code to the 0000 default value.
IF YOU LOOSE THE CODE, PLEASE CONTACT THE AUTHORISED SERVICE CENTER FOR THE TOTAL RESET OF 
THE CONTROL UNIT.

12.8) MOTOR TYPE SELECTION  (

MOT1

)

Allows to select the setting of the control unit according to the type of motor to be used.
Normally the right value is set by default and it does not need to be changed by the end user.
Only in case of control unit replacement is necessary to set the right value. Every number correspond to a defined type of motor, as 
shown in the list below.

0: YAK25
1: BULL 15 OMI 230Vac
2: BULL 15 OMAI 115Vac
3: NOT USED

For convenience the screen shows always the message MOT followed by the number of the motor currently set 
(eg. MOT.1,MOT.2)

TAB. 1

BULL 15 OMI

Kg

Max. FSTO/ FSTC

Min. TBR

Min. TSMO/TSMC

PMO/PMC

V (m/1’)

1500

120

4

45

99/99

24

1000

100

3

35

99/99

20

600

85

2

30

99/99

17,5

According to the motor type and weight of the leaf, set the value of the speed during the opening and closing phase (FSTO/FSTC), the 
maximum value of the braking TBR and the slowdown space values TSMO/TSMC.
The PMO/PMC parameters must be at 99.
BRAKE RESISTOR MUST be connected.
Exceed the recommended values may cause damage and malfunctioning. The manufacturer does not assume liability resulting from 
improper setting of values FSTO/FSTC/TBR/TSMO/TSMC.
THE REPORTED VALUES ARE APPROXIMATE AND REFERED TO A STANDARD INSTALLATION, IN ANY CASE THE INSTALLATION 
MUST BE DONE ACCORDING TO THE REGULATIONS IN FORCE (MACHINERY DIRECTIVE 2006/42/CE AND THE EUROPEAN 
STANDARDS EN 13241-1, EN 12453, EN 12445).

Содержание CP.BULL OMI

Страница 1: ...D R A F T CP BULL OMI UNIONE NAZIONALE COSTRUTTORI AUTOMATISMI PER CANCELLI PORTE SERRANDE ED AFFINI IT EN...

Страница 2: ......

Страница 3: ...S II Ch Radio L N GND GND Shield N L SCA SERVICE LIGHT 24 Vdc 0 5A BRAKE RESISTOR PHOTO TEST fig 15 OPEN CLOSE JP1 BAR Open DAS N C JP1 BAR Close DAS 8K2 U1 LD1 LD2 MOT MOT COM 15AT 250Vac 5A P3 J6 J8...

Страница 4: ...NC NO RX1 TX1 24 Vdc PHOTO COM PHOTO TEST PHOTOTEST OPEN PHOTOTEST CLOSE OPEN OPEN LOG MINV OFF LOG MINV ON OPEN OPEN LOG MINV OFF LOG MINV ON 17 SCA 24Vac AUX 0 Aux 1 L N Service Light 230V SCA 24V M...

Страница 5: ...5 OPEN Open Safety Edge COM PHOTO Close Safety Edge 8K2 N O Jumper DAS DAS MOTOR JP1 Open DAS N C JP1 Close DAS 8K2 N C 19 bar On BAR LOGIC ON...

Страница 6: ...PRG PRG PRG tca ped tsmo tsmc tm fstc sldo sldc pMo pmc seav 40 20 20 20 240 fsto 45 25 25 70 70 1 sear 1 blo 3 45 PAR PAR Power ON Display OFF Firmware Ver 3s Diagnostic LOG tca IBL IBCA SCL PP PRE h...

Страница 7: ...G dr cken Appuyez sur la touche PG Presionar la tecla PG Wcisn przycisk PG Selezionare il pulsante del trasmettitore da associare alla funzione Press the transmitter key which is to be assigned to fun...

Страница 8: ...nd EN 12453 Only use original accessories and spare parts use of non original spare parts will cause the warranty planned to cover the products to become null and void All the mechanical and electrica...

Страница 9: ...EDGE SAFETY EDGE Input Resistive Edge 8K2 JP1 DAS close Mechanical Edge N C JP1 DAS OPEN The activation of the Safety Edge stops and reverses the movement of the leaf for 3s RADIO RADIO RECEIVER Plug...

Страница 10: ...making any chang es Hold down the key or the key to accelerate the increase decrease of the values After waiting 30s the control unit quits programming mode and switches off the display 5 PARAMETERS...

Страница 11: ...X It selects the operating mode of the SCA output 0 SCA 1 Service light The contact closes for the time preset with TLS parameter The countdown starts at the inception of the opening operation 2 Area...

Страница 12: ...cm The safety edge connected to the DAS input is enabled only during the CLOSING PHASE Off The intervention of the safety edge connected to the DAS input stops and reverses the movement of the leaf f...

Страница 13: ...ode must be typed in IMPORTANT TAKE NOTE of the protection code and KEEP IT IN A SAFE PLACE for future maintenance operations To remove the code from a protected control unit enter the programming mod...

Страница 14: ...adjustable though the value TBR and it must respect the values indicated on the Table 1 IMPORTANT For the correct operation of parameters it is mandatory that the AUTOSET be carried out correctly see...

Страница 15: ...lt or error in the setting err AUTOSET ERROR If the error shows up during the stroke learning phase check the status of the inputs PP STOP PED PHOTO PHOTC DAS OPEN CLOSE and check also that the leaf r...

Отзывы: