Application/inputs and outputs
61
PEM735_D00084_00_M_XXEN/02.2015
7.7 Logic modules
The PEM575 provides six programmable logic modules which perform AND,
NAND, OR or NOR logical operations. Each logic module is capable of linking four
different setpoint conditions with each other.
Logical expression
=
{
(source 1
[mode 1]
source 2)
[mode 2]
source 3
}
[mode 3]
source 4
The alarm symbol
at the right side of the LC display appears when there are ac-
tive logic modules. Logic modules are programmed via the communications inter-
face.
Details about the applied
registers
and their data structure you will find on
.
The following
setup parameters
are provided:
1.
Activating
logic modules
2.
Mode
1…3: Specifies the type of logical evaluation to be performed (AND,
NAND, OR, NOR).
3.
Source
1…4: Specifies the source inputs (table 10.30).
4.
Trigger
: Trigger 1 and Trigger 2 specify what action the logic module will
take when it becomes active (table 10.31).
Содержание LINETRAXX PEM575 Series
Страница 8: ......
Страница 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Страница 171: ......