Installation and connection
25
PEM735_D00084_00_M_XXEN/02.2015
4.7.2
Three-phase 3-wire system
The universal measuring device PEM575 can be used in three-phase-3-wire sys-
tems.
The line voltage must not exceed AC 400 V.
Fig. 4.6: Connection diagram three-phase-3-wire system
When used in 3-wire systems, the connection type (
TYPE
) has to be set to
DELTA
(refer to page 46). For this purpose,
the measuring inputs L2 and
N
are to be
bridged
.
L1
L2
L3
PEM
R
i
AC 400 V
N