Modbus Register Map
126
PEM735_D00084_00_M_XXEN/02.2015
Tab. 10.21: Setup parameters
Register 6000 and 6001
Current input 5 A: Transformation ratio current x transformation ratio voltage < 1,000,000
Current input 1 A: Transformation ratio current x transformation ratio voltage < 5,000,000
Register 6078
is disabled if not equipped with an Ethernet port
6180
RW
Trigger 1 for transient events
UINT16
0*= none
1
…
3 = DO1…DO
4
…
19 = DR1…DR16
20 = WFR1
21 = WFR2
22 = Alarm e-mail
6181
RW
Trigger 2 for transient events
UINT16
6182
RW
Language e-mail
UINT16
0* = English
6183
RW
Backlight timeout
UINT16
0 = Display always
bright
1…60 min (3*)
6184…6187
Reserved
6188
WO
Send test e-mail
UINT16
Writing "0xFF00" to
the register sends a
test e-mail to the
specified destina-
tion e-mail address.
Register Property Description Format
Range/unit
Содержание LINETRAXX PEM575 Series
Страница 8: ......
Страница 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Страница 171: ......