Modbus Register Map
144
PEM735_D00084_00_M_XXEN/02.2015
10.15 Energy log
Tab. 10.37: Energy log registers
table 10.37: Notes:
1)
Writing "Number of measurements = 0" will disable the energy log.
Register
Property
Description
Format Range/options
7700
RW
Recording mode
UINT16
0*= disabled
1 = stop-when-full
2 = FIFO
7701
RW
Number of
measurements
1)
UINT16 0…65535 (5760*)
7702
RW
Recording interval
UINT16
0 = 5 min
1 = 10 min
2*= 15 min
3 = 30 min
4 = 60 min
7703
RW
Start-
up
time
2)
HiWord: Year
UINT16
0…99 (year- 2000)
LoWord: month
1…12
7704
RW
HiWord: Date: Day
UINT16
1…31
LoWord: Hour
1…23
7705
RW
HiWord: Minute
UINT16
0…59
LoWord: Second
0…59
7706
RW
Number of parameters (N) UINT16 0…5*
7707
RW
Parameter 1
UINT16 0 = active energy
import
1 = active energy
export
2 = reactive energy
import
3 = reactive energy
export
4 = apparent energy
0*
7708
RW
Parameter 2
UINT16
1*
7709
RW
Parameter 3
UINT16
2*
7710
RW
Parameter 4
UINT16
3*
7711
RW
Parameter 5
UINT16
4*
7712
RO
Data record size
UINT16 Unit: bytes
Содержание LINETRAXX PEM575 Series
Страница 8: ......
Страница 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Страница 171: ......