Modbus Register Map
142
PEM735_D00084_00_M_XXEN/02.2015
Tab. 10.35: Waveform recording register
table 10.35: Notes:
1)
The total capacity of the waveform recorders is 32, i.e. the total of the number of measure-
ments in WFR 1 WFR 2 must be ≤ 32. The waveform recorder is disabled when register 7600
is set to 0.
2)
Valid WFR formats (number of samples/cycle x number of cycles) are 16 x 320, 32 x 160, 64 x
80, 128 x 40 and 256 x 20.
3)
When the WFR format is 256 x 20, the number of pre-fault cycles is 0…5, otherwise the range
is 0…10.
Register Property
Description
Format
7600
RW
WFR 1
Number of measurements
1)
0*…32
7601
RW
Number of samples
2)
0 = 16
1 = 32
2 = 64
3 = 128
4*= 256
7602
RW
Number of cycles
2)
320 / 160 /
80 / 40 / 20 /
10*
7603
RW
Number of cycles before the
event
0*…10
7604
RW
WFR2
Recording depth
1)
0*…32
7605
RW
Number of samples
2)
0*= 16
1 = 32
2 = 64
3 = 128
4= 256
7606
RW
Number of cycles
2)
320* / 160 /
80 / 40 / 20
7607
RW
Pre-fault cycles
3)
0*…10
Modifying any of the registers
7600…7607
will clear the WFR log and
reset the pointer to 0.
Содержание LINETRAXX PEM575 Series
Страница 8: ......
Страница 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Страница 171: ......