Modbus settings
isoNAV685-D-B_D00264_03_M_XXEN/06.2017
59
0x30D2u
12498
Relay 2 Function 3
2
Uint16
R/W
see 0x30B7u
1…7
//InsulationAlarm
0x30D3u
12499
Response value 1
4
Uint32
R/W
1,000…
10,000,000
Ω
0x30D7u
12503
Type of mains supply
system
2
Uint16
R/W
1 = 3AC
1
0x30D8u
12504
Profiles
2
Uint16
R/W
1 = Offline
1
0x30D9u
12505
Coupling monitoring
2
Uint16
R/W
1 = Coupling monitoring off
1
0x30DBu
12507
Fault memory
2
Uint16
R/W
1 = Fault memory on
2 = Fault memory off
1…2
0x30DCu
12508
Start-up delay
2
Uint16
R/W
0…120
s
0x30DDu
12509
Activate/deactivate
device
2
Uint16
R/W
1 = Activates device
2 = Deactivates device
1…2
Register address
(hexadecimal)
Register
address
(decimal)
Description
Num-
ber
Data type
Mode
Comment
Range
Unit