![Bender ISOMETER isoNAV685-D-B Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/bender/isometer-isonav685-d-b/isometer-isonav685-d-b_manual_2731673032.webp)
Settings
Settings
isoNAV685-D-B_D00264_03_M_XXEN/06.2017
32
10.1
(1.8.1.4) Function 2
Refer to
.
10.1
(1.8.1.5) Function 3
Refer to
.
10.1
(1.8.2) Relay 2
Refer to
.
10.1
(1.8.3) Digital 1
The following parameters can be set for each of the digital outputs:
The functional test of the digital output can be activated or deactivated. This only applies
to the manual test and not to the cyclic device self test:
•on
The manual test changes the status of the digital output.
•off
The manual test does not change the status of the digital output.
10.1
(1.8.3.1) Mode
The following settings can be used to set the operating mode for the digital output:
10.1
(1.8.3.2) Function 1
Refer to
.
10.1
(1.8.3.3) Function 2
Refer to
.
10.1
(1.8.3.4) Function 3
Refer to
.
10.1
(1.8.4) Digital 2
•Active
In the active mode +24 V will be internally applied across the output.
•Passive
In the passive mode ≤ 32 V are externally connected (see technical
data). The output switches the applied potential to ground.
Observe the maximum output current!
Maximum output current in case of internal voltage supply
via A1/+ and A2/-: 200 mA in total to X1.
Also refer to the formula for calculating I
LmaxX1
in the Technical Data un-
der
“Digital Outputs (Q1, Q2)” on page 45
.
X1
iso685
Q
x
+
X1
iso685
Q
x
+
oder
X1
iso685
+
Q
x
X1
iso685
+
Q
x
internal
external