![Bender ISOMETER isoNAV685-D-B Скачать руководство пользователя страница 53](http://html.mh-extra.com/html/bender/isometer-isonav685-d-b/isometer-isonav685-d-b_manual_2731673053.webp)
Modbus settings
isoNAV685-D-B_D00264_03_M_XXEN/06.2017
53
0x1030
4144
Channel number (3)
2
Uint16
RO
0x1031
4145
Leakage capacitance
4
Float
RO
F
0x1033 - 0x103F
4147-4159
See previous channel
RO
0x1040
4160
Channel number (4)
2
Uint16
RO
0x1041 4161
System
connection
4
Float
RO
0 = O.K.
101 = Error
V
0x1043 - 0x104F
4163-4175
See previous channel
RO
0x1050
4176
Channel number (4)
2
Uint16
RO
0x1051
4177
Connection to earth
4
Float
RO
0 = O.K.
101 = Error
V
0x1053 - 0x105F
4179-4191
See previous channel
RO
0x1060
4192
Channel number (5)
2
Uint16
RO
0x1061
4193
Device error
4
Float
RO
Device error number
(e.g. 750 -> 7.50 Communication CAN)
V
0x1063 - 0x106F
4195-4207
See previous channel
RO
Register address
(hexadecimal)
Register
address
(decimal)
Description
Num-
ber
Data type
Mode
Comment
Range
Unit