Modbus settings
isoNAV685-D-B_D00264_03_M_XXEN/06.2017
56
//Time
0x3098u
12440
Time
4
Unix Time
R/W
0x309Au
12442
0
4
0
R
0x309Cu
12444
Time zone
4
Float
R/W
Time zone offset
-12…13
h
0x309Eu
12446
NTP on/off
2
Uint16
R/W
1 = NTP on
0 = NTP 0ff
1…2
0x309Fu
12447
NTP server IP
4
Uint32
R/W
IP address of the NTP server
aaa.bbb.ccc.ddd => aaa*256³
+ bbb*256² + ccc*256 + ddd
0…
4.294.967.295
0x30A1u
12449
Date format
2
Uint16
R/W
1 = d.m.y
2 = m.d.y
1…2
0x30A2u
12450
Summertime
2
Uint16
R/W
1 = off
2 = DST
3 = CEST
1…3
0x30A3u
12451
Time format
2
Uint16
R/W
1 = 12 h
2 = 24 h
1…2
//BMS
0x30A4u
12452
BMS address
2
Uint16
R/W
BMS address
1…90
//DigitalInFunctions
0x30A5u
12453
Digital Input 1
Function
2
Uint16
R/W
1 = Off
2 = Test
3 = Reset
4 = Deactivate device
5 = Start initial measuring
1…5
0x30A6u
12454
Digital Input 1
Mode
2
Uint16
R/W
1 = active high
2 = active low
1…2
0x30A7u
12455
Digital Input 1
T(on)
4
Float
R/W
ON delay because of debounce
0.1…300
s
0x30A9u
12457
Digital Input 1
T(off )
4
Float
R/W
OFF delay because of debounce
0.1…300
s
Register address
(hexadecimal)
Register
address
(decimal)
Description
Num-
ber
Data type
Mode
Comment
Range
Unit