Modbus settings
isoNAV685-D-B_D00264_03_M_XXEN/06.2017
54
//ReadOnly
0x2000u
8192
Insulation vaue 1
4
Float
RO
Ω
0x2002u
8194
Insulation vaue 2
4
Float
RO
Ω
0x2004u
8196
Insulation vaue 3
4
Float
RO
Ω
0x2018
8216
System connection
4
Float
RO
0 = O.K.
101 = Error
0x201A
8218
Connection to earth
4
Float
RO
0 = O.K.
101 = Error
0x201C
8220
Device error
4
Float
RO
Device error number
(e.g. 750 -> 7.50 Communication CAN)
0x202A
8234
Duration of measuring
pulse
4
Float
RO
0 % = Measuring pulse has switched
100 % = Measuring pulse just before swit-
ching
%
0x2FFEu
12286
Actual IP Address
4
UInt32
RO
Currently used IP address
aaa.bbb.ccc.ddd => aaa*256³
+ bbb*256²+ ccc*256 + ddd
%
//IP-Configuration
0x3000u
12288
DHCP on/off
2
Uint16
R/W
1 = DHCP on
2 = DHCP off
1…2
0x3001u
12289
IP Address
4
Uint32
R/W
Configured IP address (used when DHCP =
off )
aaa.bbb.ccc.ddd =>
aaa*256³+ bbb*256² +
ccc*256 + ddd
0…
4.294.967.295
0x3003u
12291
Standard Gateway
4
Uint32
R/W
Configured gateway (used when DHCP =
off )
aaa.bbb.ccc.ddd =>
aaa*256³+ bbb*256² +
ccc*256 + ddd
0…
4.294.967.295
Register address
(hexadecimal)
Register
address
(decimal)
Description
Num-
ber
Data type
Mode
Comment
Range
Unit