![Bender ISOMETER iso685-D-B Скачать руководство пользователя страница 65](http://html.mh-extra.com/html/bender/isometer-iso685-d-b/isometer-iso685-d-b_manual_2731649065.webp)
Technical data
Technical data
iso685-x-B_D00177_07_M_XXEN/07.2019
65
Display
Indication ....................................................................................................................... graphic display 127 x 127 pixels, 40 x 40 mm
2)
Display range measured value.........................................................................................................................................0.1 kΩ…20 MΩ
Operating uncertainty (acc. to IEC 61557-8)................................................................................................................ ±15 %, min. 1 kΩ
LEDs
ON (operation LED) ............................................................................................................................................................................green
SERVICE............................................................................................................................................................................................. yellow
ALARM 1 ........................................................................................................................................................................................... yellow
ALARM 2 ........................................................................................................................................................................................... yellow
Inputs/outputs (X1-Interface)
Cable length X1 (unshielded cable) .............................................................................................................................................. ≤ 10 m
Recommended cable (shielded, shield connected to PE on one side: J-Y(St)Y min. 2x0.8)..................................................... ≤ 100 m
Total max. supply output current via X1.+/X1.GND for each output..........................................................................................max. 1 A
Total max. supply output current via A1/A2 in total on X1 .................................................................................................max. 200 mA
Total max. supply output current via A1/A2 in total on X1 between 16.8 V and 40 V ............................................................................
.............................................................................................................................................................I
LmaxX1
= 10mA + 7mA/V *
U
s
3)
............................................................................................................................................(negative values are not allowed for
I
LmaxX1
)
Digital inputs (I1, I2, I3)
Number...................................................................................................................................................................................................... 3
Operating mode, adjustable................................................................................................................................... active high, active low
Functions ..................................................................................................... off, test, reset, deactivate device, start initial measurement
Voltage...........................................................................................................................................Low DC -3…5 V, High DC 11…32 V
Voltage tolerance ...........................................................................................................................................................................± 10 %
Digital outputs (Q1, Q2)
Number...................................................................................................................................................................................................... 2
Operating mode, adjustable active, passive
Functions .........................................off, Ins. alarm 1, Ins. Alarm 2, connection fault, DC- alarm
4)
, DC+ alarm
4)
, symmetrical alarm,
........................................................................ device fault, common alarm, measurement complete, device inactive, DC offset alarm
Voltage passive.............................................................................................................................DC 0…32 V, active DC 0/19.2…32 V
Analogue output (M+)
Number...................................................................................................................................................................................................... 1
Operating mode................................................................................................................................linear, midscale point 28 kΩ/120 kΩ
Functions .............................................................................................................................................................insulation value, DC shift
Current 0...20 mA (< 600 Ω), 4…20 mA (< 600 Ω), 0…400 μA (< 4 kΩ)
Voltage 0…10 V (>1 kΩ), 2…10 V (>1 kΩ)
Tolerance related to the current/voltage final value ....................................................................................................................± 20 %
Interfaces
Field bus:
Interface/protocol.................................................................................................................................... web server/Modbus TCP/BCOM
Data rate........................................................................................................................................................... 10/100 Mbit/s, autodetect
Max. amount Modbus requests ....................................................................................................................................................< 100/s
Cable length .................................................................................................................................................................................≤ 100 m
Connection ........................................................................................................................................................................................... RJ45
IP address .................................................................................................................................................... DHCP/manual* 192.168.0.5*
Network mask ...................................................................................................................................................................255.255.255.0*
BCOM address...........................................................................................................................................................................system-1-0
Function ..............................................................................................................................................................communication interface
ISOnet
Number of ISOnet devices ........................................................................................................................................................2…20 dev
Maximum nominal system voltage ISOnet ............................................................................................................AC, 690 V/DC, 1000 V
ISOloop
ISOloop devices.........................................................................................................................................................................2…10 dev
Sensor bus:
Interface/protocol ..............................................................................................................................................................RS-485/BB bus
Data rate mode 1 ..................................................................................................................................................................... 9.6 kbaud/s
Cable length (depending on the baud rate)..............................................................................................................................≤ 1200 m
Cable: twisted pair, one end of shield connected to PE................................................................... recommended: J-Y(St)Y min. 2x0.8
Connection ................................................................................................................................................................. terminals X1.A, X1.B
Terminating resistor............................................................................................................................120 Ω, can be connected internally
Device address .................................................................................................................................................................................1…90
Switching elements
Number of switching elements..............................................................................................................................2 changeover contacts
Operating mode.......................................................................................................................................... N/C operation/N/O operation
Contacts 11-12-14 / 21-22-24.........................................off, ins. alarm 1, ins. alarm 2, connection fault, DC- alarm
4)
, DC+ alarm
4)
............................................................................................ symmetrical alarm, device fault, common alarm, measurement complete,
...................................................................................................................................................................device inactive, DC offset alarm
Electrical endurance under rated operating conditions, number of cycles.................................................................................... 10.000
Contact data acc. to IEC 60947-5-1:
Utilisation category................................................................................................................... AC-13 / AC-14 / DC-12 / DC-12 / DC-12
Rated operational voltage .............................................................................................................. 230 V / 230 V / 24 V / 110 V / 220 V
Rated operational current ........................................................................................................................... 5 A / 3 A / 1 A / 0.2 A / 0.1 A
Rated insulation voltage ≤ 2000 m NN ........................................................................................................................................... 250 V
Rated insulation voltage ≤ 3000 m NN ........................................................................................................................................... 160 V
Minimum contact rating ...................................................................................................................................... 1 mA at AC/DC ≥ 10 V