Device communication
iso685-x-B_D00177_07_M_XXEN/07.2019
46
10.7.1 isoData-protocol table
Description
Length [Bytes] Value
Unit
Example string
Mode
1
2
3
Data packet start character
for modes 2 and 3
1
!
!
-
0
0
Data packet start character
for mode 1
1
0x02
0x02
0
-
-
Available Bitmask
8
Dependent on the fields included. (Bitmask)
FFFFFFFF
-
-
1
Date
8
Current date
dd.mm.yy
-
-
2
Time
12
Current time
hh:mm:ss:mmm
-
-
3
Insulation fault location
1
' ' = symmetrical fault
'+' = Fault on L1/+
'–' = Fault on L3/-
x
-
1
-
Isolation fault location
Detailed overview
4
Insulation fault percentage distribution from
100 … +100
%
+123
-
8
4
Isolation fault location
Brief overview
1
0 = AC fault
1 = DC- fault
2 = DC+ fault
0
6
-
-
Insulation resistance
Brief overview
6
R
F
kΩ
123456
1
-
-
insulation resistance
Limited overview
6
R
F
Note: Value limited to 9.9 MΩ
kΩ
1234.5
-
2
-
insulation resistance
Detailed overview
9
R
F
Note: Value limited to 9.9 GΩ
kΩ
1234567.8
-
-
5
Measured value counter
2
Increased with each new measured value.
Integer overflow at 99.
12
-
11
6
Leakage capacitance Ce
4
R Mode [μF] Z Mode [nF]
Note: Z Mode is not supported.
μF (R-Mode)
nF (Z-Mode)
1234
-
3
7
Voltage
U
n
(VRMS) L1-L2
7
Voltage bewteen phase L1 and phase L2.
RMS value, unsigned.
V
12345.6
-
-
8
Voltage
U
n
(VRMS) L1-L3
7
Voltage between phase L1 and phase L3.
RMS value, unsigned.
V
12345.6
-
-
9
Voltage
U
n
(VRMS) L2-L3
7
Voltage between phases L2 and L3.
RMS value, unsigned.
V
12345.6
-
-
10
Voltage
U
n
(VRMS)
5
Voltage between phases L1 and L2.
RMS value, signed AC Net ' '
DC system always signed with '+'
V
+1234
-
5
-
Voltage
U
n
(VRMS) L1-PE
5
Voltage between phase L1 and PE.
RMS value, Note: always signed with '+'
V
1234
-
6
11