Settings
Settings
iso685-x-B_D00177_07_M_XXEN/07.2019
36
9.2
(2.0) Data measured values
The ISOMETER® stores certain measured values for a specific period of time. You can view
these data in the "Data meas. value" menu. Navigate through the different views using
the
and
buttons:
9.2
(3.0) Control
Control of the device during operation:
9.2
(3.1) TEST
Starts a manual device test.
9.2
(3.2) Reset
Reset of fault and alarm messages.
9.2
(3.3) Start initial measurement
All recorded measurements are discarded and a new measurement is started
9.2
(3.4) Device:
Insulation resistance measurement function of the ISOMETER® active or inactive:
1. isoGraph data
Displays the insulation resistance and chronological sequence.
1.1 Scaling: Hour
1.2 Scaling: Day
1.3 Scaling: Week
1.4 Scaling: Month
1.5 Scaling: Year
2. Insulation data
Displays the current insulation resistance, the minimum insulation
resistance measured and the system leakage capacitance.
3. IT system data
Displays the system phase-to-phase voltages and the mains fre-
quency (r.m.s. values)
4. IT system data
Displays the system phase-to-earth voltages
1. TEST
2. Reset
3. Start initial measurement
4. Device:
5. ISOnet priority
•Aktiv
The device is active.
•Inaktiv
Display shows message
Device inactive
. No monitoring of the IT system!
9.2
(3.5) ISOnet priority
Assigns priority to a device in ISOnet mode for a period of 12 hours. While the priority is
active, all other devices in ISOnet mode are inactive. Priority can be withdrawn at any
time. After 12 hours, automatic switchover to normal ISOnet operation takes place.
9.2
(4.0) History
In the history menu, the faults detected by the ISOMETER® are displayed.
9.2
(5.0) Device settings
Basic settings of the ISOMETER®.
9.2
(5.1) Language
Selecting the display language:
9.2
(5.2) Clock
Setting the time and date display format.
9.2
(5.2.1) Time
Setting the time format to 24 hours or 12 hours am/pm.
9.2
(5.2.2) Format (time)
Selecting the appropriate time format to be displayed:
•History
Overview of faults that have occurred.
•Delete
Reset the history memory.