Technical data
Technical data
iso685-x-B_D00177_07_M_XXEN/07.2019
63
14.3 Factory settings iso685-x-B
Parameter
Wert
Response values/alarms
Response value
R
an1
(ALARM 1)
40 k
Ω
Response value
R
an2
(ALARM 2)
10 k
Ω
DC alarm
off
DC offset voltage for DC alarm
65 V
Fault memory
off
Coupling monitoring
on
System
System type
3AC
System profile
Power circuit
Time response
Start-up delay
T
start-up
≤ 0 s
Digital inputs
Digital input 1
Mode (operating mode)
Active high
Function
TEST
Digital input 2
Mode (operating mode)
Active low
Function
RESET
Digital outputs
Digital output 1
Function 1
off
Function 2
off
Function 3
off
Digital output 2
Function 1
off
Function 2
off
Function 3
off
Switching elements
Relay 1
Test
on
Relay mode
N/C operation
Function 1
Ins. alarm 1
Function 2
Connection fault
Function 3
off
Relay 2
Test
on
Relay mode
N/C operation
Function 1
Ins. alarm 2
Function 2
Device fault
Interface
DHCP
off
IP-Address
192.168.0.5
Subnetzmask
255.255.255.0
BCOM-Adress
system-1-0
Geräteaddress BS-Bus
1
isoData
Mode 1
Modbus RTU
Address
100
Baudrate
19,2 kBaud
Parity
even
Stoppbits
1
ISOnet
off
ISOloop
off
Parameter
Wert