Operation and setting
79
IRDH575_D00089_05_M_XXEN/01.2020
6.12 Menu SERVICE
This menu item is provided for the Bender service personnel and is protected
by a password against erroneous settings. It is intended to provide fast fault
clearance by qualified experts in the event of a device error.
6.13 Parameterization via Internet
The parameters of an IRDH575 indicated below can be checked and set from
a remote place of use by using a personal computer. In addition, a browser
(viewing program for Internet application) and our protocol converter
FTC470XET (BMS <==> Ethernet/TCP/IP) are required.
Remote setting is, for example, possible for:
Response value Alarm 1 (1 kΩ…10 MΩ)
Response value Alarm 2 (1 kΩ…10 MΩ)
Operating principle alarm relay K1 (e.g. N/O operation)
Operating principle alarm relay K2 (e.g. N/O operation)
Measuring principle (AMP or DC)
Current output ranges for external measuring instruments (0/4…20
mA)
Maximum system leakage capacitance (150 µF or 500 µF)
Time for repetition of the automatic self test (off/ 1 h/ 24 h)
Starting time of the automatic self test (0.00…23.00 h)
Language of the alarm messages to be displayed (D, GB)
Setting the fault memory to ON or OFF
EDS mode (on, off, auto, 1 cycle), start and stop conditions for the EDS
systems
EDS type of system (DC, AC, 3 AC)
EDS max. test current (1 / 2.5 / 10 / 25 / 50 mA)
EDS Position Mode address (BMS address of the EDS47… to be
requested)
EDS Position Mode channel (BMS channel of the EDS47… to be
requested)