Operation and setting
54
IRDH575_D00089_05_M_XXEN/01.2020
6.4.5
Current output for external measuring instruments
Factory setting: 0…20 mA
The current output of the IRDH575 can be set to "0…20 mA" or "4…20 mA" via
the menu point "M+/M-:". The maximum load is 500 Ω.
Function 0…20 mA:
R
F
= insulation fault,
I = current in mA
Function 4…20 mA:
R
F
= insulation fault,
I = current in mA
The associated characteristic curves are illustrated on page 98.