Serial interfaces
84
IRDH575_D00089_05_M_XXEN/01.2020
If no flashing point appears, it may be attributed to the following:
No Master available in the network
More than one Master available in the network
RS-485 interface (terminal A/B) not connected or reversed
7.3.3
BMS operation in the Standby mode
The BMS function of the Master ISOMETER® is completely available in the
standby mode (Stand-by: F1/F2 bridged).
The function ISO Monitor in the COM menu can be used to request data from
other bus nodes, for example:
Actual insulation values of other SLAVE ISOMETER®s connected to the
BMS bus
Fault messages of all SLAVE devices connected to the BMS bus
In the Slave mode, the functions of the EDS470 menu and
the position mode in the EDS SETUP menu are not available!
Both functions are only available in the Master mode.