4.5.2
ALARMS
ALARMS
CONDITION
HELP MESSAGE
Overload X Failure
Check AMP draw, use manual reset if OK
High Suction PSI
High suction pressure – check suction
pressure and trip point
Low Suction PSI
Low suction detected – check suction
pressure and trip point
High System PSI
High pressure detected in the system –
check trip point
Low System PSI
Low pressure detected in the system –
check PRV and set point
Water Level Low
Check water level in holding tank
Water Temp High
Check water temperature
Pump X Off
Need pump in system – if OK enable pump
Suction Trans Fail
Check wiring, piping, polarity, and continuity
System Trans Fail
Check wiring, piping, polarity, and continuity
Flow Trans Fail
Check wiring, piping, polarity, and continuity
Suction RTD1 Fail
Check wiring, continuity
System RTD2 Fail
Check wiring, continuity
Power Fail
Check cable connections and plug insertions
Pump X Failure
Check DP switch, impeller, coupler, motor
Remote Contact Open
➀
7 Day Timer Off
➀
NOTES:
➀
Bottom line only. No help message.
14