10
Default
Allowable
Field
Line #
DISPLAY
➀
Value
Range
Values
12
Pump 2 AMPs 0
Enter Motor #2 nameplate FLA
0
0 - 175
13
Pump 3 AMPs 0
Enter Motor #3 nameplate FLA
0
0 - 175
14
Pump #1 GPM 0
Enter Staging GPM of Pump #1
0
0 - 30,000
15
Pump #2 GPM 0
Enter Staging GPM of Pump #2
0
0 - 30,000
16
Pump #3 GPM 0
Enter Staging GPM of Pump #3
0
0 - 30,000
17
1 - 2 Stage % 80
Enter percent of NPHP, NPFLA, or GPM to stage 2nd
pump in sequence
80
0 - 100
18
2 - 3 Stage % 80
Enter percent of NPHP, NPFLA or GPM to stage 3rd
pump in sequence
80
0 - 100
19
Destage % 90
Enter percent of stage percent for destaging with HP,
AMPs, or GPM only
90
0 - 99
20
Staging PSI 0
Enter pressure to stage in PSI mode after entering system
0
0 - System Span
pressure span (see Line 38)
21
Destaging PSI
Enter pressure to destage in PSI mode after entering system
0
0 - System Span
pressure span (see Line 38)
22
Forced Destg Tmr. 60
Enter in minutes (0 - 99) value of a timer after which the
60
0 - 99
pump will be forced to de-stage; ‘0’ disables this function
23
GPM Xmiter Span
Enter value equal to GPM transmitter calibration
0
0 - 30,000
24
2nd Stage Proof 2
2nd pump stage proof time in seconds
5
1 - 180
25
3rd Stage Proof 2
3rd pump stage proof time in seconds
5
1 - 180
26
Display Watts YES
Use up/down keys to enter yes or no
Yes
Y/N
27
Three phase Watts YES
Use up/down keys to enter yes or no, YES = three phase,
Yes
Y/N
NO = single phase
28
Display AMPs YES
Use up/down keys to enter yes or no
Yes
Y/N
29
Display GPM No
Use up/down keys to enter yes or no
No
Y/N
30
Suction Press. Span 100
Enter value equal to suction pressure span
100
0 - 999
31
High Suct. Press. 0
Enter value of the high suction pressure above which an
0
0 - 100
alarm will be set
32
High Suct. Pr. TMR. 0
Enter in seconds (0 - 999) value of high suction cutout
0
0 - 999
proof timer, ‘0’ disables this function
33
High Suct. Reset 0
Enter value of the high suction reset pressure
0
0 - 100
34
Low Suct. Press. 5
Enter value of the low suction pressure below which an
5
0 - 100
alarm will be set
35
Low Suct. Pr. TMR. 20
Enter in seconds (0 - 999) value of low suction proof timer;
20
0 - 999
‘0’ disables this function
36
Low Suct. Reset 10
Enter value of the low suction reset pressure
10
0 - 100