background image

Wiring diagrams

AC/DC 24 V, modulating

Y   

U

1

3

2

5

– + 

T

~

DC

 

(0)2…10

 

V

DC

 

2…10

 

V

Cable colours:

1 = black 

2 = red 

3 = white 

5 = orange

Signal cable lengths

Y U

1

3

2

5

T

~

A

C

L

tot

L

1

L

2

L

2

T

 / 

~

L

tot

 = L

1

 + L

2

AC

DC

0.75 mm

2

≤30 m

≤5 m

1.00 mm

2

≤40 m

≤8 m

1.50 mm

2

≤70 m

≤12 m

2.50 mm

2

≤100 m

≤20 m

A = actuator

C = control unit

L1 = actuator connecting cable 

L2 = customer cable 

Ltot = maximum signal cable length

 

Note:

 

 

In the event of several actuators 

switched in parallel, the maximum 

signal cable length is to be divided 

by the number of actuators.

L

N

Y U

T

A

C

AC 24 V

AC 230 V

L

1

A = actuator 

C = control unit 

L1 = actuator connecting cable

 

Note:

 

If supply and data line are handled 

separately, then no special 

limitations apply for the installation.

Functions

Functions with basic values (conventional mode)

Override control with AC 24 V with relay contacts

Override control with AC 24 V with rotary switch

a

b

c

0%

ZS 50% 

100% 

Y

a

b

c

~

T

Y (DC 0...10 V)

e.g. 1N 4007

1

2

3

5

Y U

~

T

e.g. 1N 4007

1

2

3

5

Y U

0% ZS 50% 100%

(DC 0...10 V)

SMQ24G-SR

Damper actuator, IP66, Modulating, AC/DC 24 V, 16 Nm, 

Running time motor 7 s

Electrical installation

www.belimo.eu

SMQ24G-SR • en-gb • 2015-10-16 • subject to changes

4

!

Notes

•  Connection via safety isolating transformer.

•  Parallel connection of other actuators possible. Observe the performance data.