background image

Wiring

Wiring

On/Off, Floating Point

®

1

2

4

24 VAC Transformer

a open
a closed

             The indication of direction 
is valid for switch position 1.

Blk   (1)   Common

Red  (2)   +

     

Wht  (3)   +

a

Line
Volts

1

0

5

W266

1

2

4

24 VAC Transformer

             The indication of direction 
is valid for switch position 1.

Blk   (1)   Common

Red  (2)   +

     

Wht  (3)   +

Line
Volts

1

0

W267

On/Off

4

3

Vlt   (S1)

Red (S2)

Wht (S3)

NC

NO

0 to 95

W268

Floating Point or On/Off control

4

Auxiliary Switch of 
LMB24-3-S and 
AMB24-3-S

Notes:

Provide overload protection and disconnect as required.

 

Actuators may also be powered by 24 VDC for a 24V power supply.

For end position indication, interlock control, fan startup, etc., 
xMB24-3-S incorporates one built-in auxiliary switches: 
1 x SPDT, 3A (0.5A) @250 VAC, UL listed, adjustable 0° to 95°.

Meets cULus requirements without the need of an electrical 
ground connection.

For 100 to 240 VAC no transformer is required.

1

2

3

4

5

Torque

(based on 4 in-lb per sq. ft)

Running 

Time

Power 

Supply

Power 

Consumption

Feedback

Airside
Products

35 in-lb [4 Nm],

 

Apprx. 11 sq. ft.

45 in-lb [5 Nm],

 

Apprx. 11 sq. ft.

70 in-lb [8 Nm],

Apprx. 22 sq. ft.

90 in-lb [10 Nm],

Apprx. 22 sq. ft.

140 in-lb [15 Nm]

Apprx. 45 sq. ft.

180 in-lb [20 Nm],

 

Apprx. 45 sq. ft.

360 in-lb [40 Nm],

 

Apprx. 90 sq. ft.

Motor Drive 

(Default)

24 

VAC +/- 20%,

 

VDC +/- 15%

100 to 240 

VA

C

VA

 r

ating

W

attage running 

(holding)

5 k

Ω

 Resistive

10 k

Ω

 Resistive

GMB24-3

150

6

4 (2.0)

GMX24-3

150

6

4 (2.0)

GMX120-3

150

7

4 (2.0)

AMB24-3

95

5.5

2.5 (0.2)

AMB24-3-S

95

5.5

2.5 (0.2)

AMX24-3

 

95

5.5

2.5 (0.2)

AMX24-3-T

95

5.5

2.5 (0.2)

AMX120-3

95

7

3 (0.6)

AMQB24-1

7

18

12 (1.5)

AMQX24-1

7

18

12 (1.5)

NMB24-3

95

4

2 (0.2)

NMX24-3

95

4

2 (0.2)

NMX24-3-T

95

4

2 (0.2)

NMX120-3

95

7

3 (0.6)

NMQB24-1

4

18

12 (1.5)

NMQX24-1

4

18

12 (1.5)

LMB24-3

95

2

1.5 (0.2)

LMB24-3.1

95

2

1.5 (0.2)

LMB24-3-S

95

2

1.5 (0.2)

LMB24-3-T

95

2

1.5 (0.2)

LMB24-3-T.1

95

2

1.5 (0.2)

LMB24-3-P5-T

95

2

1.5 (0.2)

LMX24-3-P5-T.1

95

2

1.5 (0.2)

LMX24-3-P10-T

95

2

1.5 (0.2)

LMX24-3

95

2

1.5 (0.2)

LMX24-3-T

95

2

1.5 (0.2)

LMX120-3

95

4

2 (0.5)

LMQB24-1

2.5

18

12 (1.5)

LMQX24-1

2.5

18

12 (1.5)

Содержание AMB series

Страница 1: ...ch in position 0 the actuator rotates counterclockwise with a decrease in voltage or current The non spring return rotates clockwise when the switch is in the 1 position and power is applied to wire 2...

Страница 2: ...11 16 1 5 6 to 7 ft lb AMB 1 2 to 1 05 3 8 to 11 16 1 5 6 to 7 ft lb AMQB 1 2 to 1 05 7 16 to 11 16 1 5 6 to 7 ft lb GMB 1 2 to 1 05 7 16 to 11 16 1 5 6 to 7 ft lb LMB standard clamp has max 5 8 diam...

Страница 3: ...8 between stop and clamp Tighten the two nuts on the universal clamp with a 8 10 or 12mm wrench see table column D on page 2 for required torque 5 Snap on the reflective position indicator Adjust end...

Страница 4: ...orque based on 4 in lb per sq ft Running Time Power Supply Power Consumption Feedback Airside Products 35 in lb 4 Nm Apprx 11 sq ft 45 in lb 5 Nm Apprx 11 sq ft 70 in lb 8 Nm Apprx 22 sq ft 90 in lb 1...

Страница 5: ...signal to 2 to 10 VDC up to 2 actuators may be connected in parallel Only connect common to neg leg of control circuits 1 2 3 4 5 Torque based on 4 in lb per sq ft Running Time Power Supply Power Cons...

Страница 6: ...4 VAC Transformer Blk 1 Common Wht 2 Hot Wht 3 Y1 Input Pnk 4 Y2 Input Org 5 U Output 2 to 10V 1 3 6 4 2 A B 8 9 Notes W399 Provide overload protection and disconnect as required Actuators may be conn...

Страница 7: ...r may also be powered by 24 VDC Actuators and controller must have separate transformers Consult controller instruction data for more detailed installation information Resistor value depends on the ty...

Страница 8: ...erations Mechanical Features Mechanical Angle of Rotation Limiting The adjustable stops are needed when there is no damper stop or if you want the damper to stop rotating before it reaches its stops T...