background image

3

Mounting Installation 

Reversible Clamp Quick Mount  (NM, AM, GM)

®

1.  Turn the damper shaft until the blades are 

fully closed.

2. 

①  

Slip the actuator’s universal clamp over the 
damper shaft.  Make sure that the duct and 
the controls on the cover are accessible.  
Place the actuator in the desired mounting 
position.

 

➁   

Hand tighten the two nuts on the actuators 
universal clamp. 

3. 

①  

Disengage the actuator gear train by 
pressing the manual override button and 
rotate the clamp until centered.  

 

➁  

Slide the anti-rotation strap up under the 
actuator so it engages the actuator at the 

center of the cutout

. Bend the bracket as 

needed to support the rear of the actuator.  
Secure to ductwork with self-tapping 
screws (No. 8 recommended).

4. 

①  

Loosen the nuts on the universal clamp.  
Press the manual override button and 
rotate the clamp to about 5° from the 
closed position (1/16 to 1/8” between stop 
and clamp).  

 

➁  

Tighten the two nuts on the universal 
clamp with a 8, 10 or 12mm wrench 
(see table, column D on page 2 for 
required torque).

5. 

① 

Snap on the reflective position indicator.

 

➁ 

Adjust end-stops, if required

6.  Mount actuators indoors.  If mounted out-

doors, use approved protective enclosure.  

The damper is now fully closed but the actuator 
is 5° from fully closed.  This is called “pre-load-
ing” the actuator.  When the actuator is powered 
and sent to the closed position: it will put its full 
torque on the shaft compressing the edge and 
blade seals.  This ensures that the damper will 
meet its leakage rating.  The actuator is elec-
tronically protected from overload and will not be 
damaged.

Testing the installation without power

1. 

Disengage the gear train with the manual 
override button and move the shaft from 
closed to open to closed.  Ensure that there 
is no binding and that the damper goes fully 
open and closes with 5° of actuator stroke 
left.

2. 

Correct any problems and retest.

Standard Mounting

Center the 

anti-rotational 
bracket in the 

slot.

Содержание AMB series

Страница 1: ...ch in position 0 the actuator rotates counterclockwise with a decrease in voltage or current The non spring return rotates clockwise when the switch is in the 1 position and power is applied to wire 2...

Страница 2: ...11 16 1 5 6 to 7 ft lb AMB 1 2 to 1 05 3 8 to 11 16 1 5 6 to 7 ft lb AMQB 1 2 to 1 05 7 16 to 11 16 1 5 6 to 7 ft lb GMB 1 2 to 1 05 7 16 to 11 16 1 5 6 to 7 ft lb LMB standard clamp has max 5 8 diam...

Страница 3: ...8 between stop and clamp Tighten the two nuts on the universal clamp with a 8 10 or 12mm wrench see table column D on page 2 for required torque 5 Snap on the reflective position indicator Adjust end...

Страница 4: ...orque based on 4 in lb per sq ft Running Time Power Supply Power Consumption Feedback Airside Products 35 in lb 4 Nm Apprx 11 sq ft 45 in lb 5 Nm Apprx 11 sq ft 70 in lb 8 Nm Apprx 22 sq ft 90 in lb 1...

Страница 5: ...signal to 2 to 10 VDC up to 2 actuators may be connected in parallel Only connect common to neg leg of control circuits 1 2 3 4 5 Torque based on 4 in lb per sq ft Running Time Power Supply Power Cons...

Страница 6: ...4 VAC Transformer Blk 1 Common Wht 2 Hot Wht 3 Y1 Input Pnk 4 Y2 Input Org 5 U Output 2 to 10V 1 3 6 4 2 A B 8 9 Notes W399 Provide overload protection and disconnect as required Actuators may be conn...

Страница 7: ...r may also be powered by 24 VDC Actuators and controller must have separate transformers Consult controller instruction data for more detailed installation information Resistor value depends on the ty...

Страница 8: ...erations Mechanical Features Mechanical Angle of Rotation Limiting The adjustable stops are needed when there is no damper stop or if you want the damper to stop rotating before it reaches its stops T...

Отзывы: