background image

2

Installation Instructions

Quick-Mount Visual Instruction for Mechanical Installation

®

C

A

B

1

1

2

5

10

D

2

1

See next page for standard mounting instructions.

 A*  B 

C** 

D

LMB 

1/4” to 5/8” 

5/16” to 9/16” 

1.5” 

4 to 5 ft-lb

LMQB 

1/2” to 1.05” 

3/8” to 11/16” 

1.5” 

6 to 7 ft-lb

NMB 

1/2” to 1.05” 

3/8” to 11/16” 

1.5” 

6 to 7 ft-lb

NMQB  1/2” to 1.05” 

3/8” to 11/16” 

1.5”  

6 to 7 ft-lb

AMB 

1/2” to 1.05” 

3/8” to 11/16” 

1.5”  

6 to 7 ft-lb

AMQB  1/2” to 1.05” 

7/16” to 11/16” 

1.5” 

6 to 7 ft-lb

GMB 

1/2” to 1.05” 

7/16” to 11/16” 

1.5” 

6 to 7 ft-lb

*LMB standard clamp has max 5/8” diameter.  Accessory clamp 
K-LM20 can be mounted for sizes up to 3/4” diameter.  NM and 
AM clamps have an insert that self-centers on the following 
diameter shafts: 1/2” (default), 3/4” and 1.05”. GM clamps have 
an insert that self-centers on 3/4” diameter.

**Shorter with reversible clamp for NMB, AMB, and GMB

1

2

3

5

4

LM Universal

Mounting Bracket

Содержание AMB series

Страница 1: ...ch in position 0 the actuator rotates counterclockwise with a decrease in voltage or current The non spring return rotates clockwise when the switch is in the 1 position and power is applied to wire 2...

Страница 2: ...11 16 1 5 6 to 7 ft lb AMB 1 2 to 1 05 3 8 to 11 16 1 5 6 to 7 ft lb AMQB 1 2 to 1 05 7 16 to 11 16 1 5 6 to 7 ft lb GMB 1 2 to 1 05 7 16 to 11 16 1 5 6 to 7 ft lb LMB standard clamp has max 5 8 diam...

Страница 3: ...8 between stop and clamp Tighten the two nuts on the universal clamp with a 8 10 or 12mm wrench see table column D on page 2 for required torque 5 Snap on the reflective position indicator Adjust end...

Страница 4: ...orque based on 4 in lb per sq ft Running Time Power Supply Power Consumption Feedback Airside Products 35 in lb 4 Nm Apprx 11 sq ft 45 in lb 5 Nm Apprx 11 sq ft 70 in lb 8 Nm Apprx 22 sq ft 90 in lb 1...

Страница 5: ...signal to 2 to 10 VDC up to 2 actuators may be connected in parallel Only connect common to neg leg of control circuits 1 2 3 4 5 Torque based on 4 in lb per sq ft Running Time Power Supply Power Cons...

Страница 6: ...4 VAC Transformer Blk 1 Common Wht 2 Hot Wht 3 Y1 Input Pnk 4 Y2 Input Org 5 U Output 2 to 10V 1 3 6 4 2 A B 8 9 Notes W399 Provide overload protection and disconnect as required Actuators may be conn...

Страница 7: ...r may also be powered by 24 VDC Actuators and controller must have separate transformers Consult controller instruction data for more detailed installation information Resistor value depends on the ty...

Страница 8: ...erations Mechanical Features Mechanical Angle of Rotation Limiting The adjustable stops are needed when there is no damper stop or if you want the damper to stop rotating before it reaches its stops T...