8.2.1 Extended parameters
The following table represents extended parameters of the IO-Link ports.
SDO
SDO content
Index
Size
Index
Size
Type
Name (specification)
0x23n0:1 1
UINT8
Data Storage
0 = Data Storage disabled (stored data set
is preserved)
1 = Data Storage download only (IOLM →
IOLD)
2 = Data Storage upload only (IOLD →
IOLM)
3 = Data Storage download and upload
4 = Data Storage disabled and cleared (a
previously stored data set is cleared)
Others: reserved
0x23n0
2
0x23n0:2 1
UINT8
Fail Safe Mode
0 = Set Low
1 = Set High
2 = Hold Last Value
3 = Replacement value (refer object 0x2301)
4 = IO-Link master command
Others: reserved
Key: