13 Technical data
13.5 IO-Link Master ports Class A,
Pin 4
13.5.2 Configured as a digital output
Attention:
For LioN-X variants, the power for the outputs is supplied
via the U
L
power supply.
Attention:
For LioN-Xlight variants, the power for the outputs is
supplied via the U
S
power supply.
Output type
normally open, p-switching
Nominal output current per
channel
Signal status “1”
Signal status “0”
min. (U
L
-1 V)
max. 2 V
0980 XSL 3912-121...
16 A (M12 Power)
0980 LSL 3x11-121...
4 A
Max. output current per
device
0980 LSL 3x10-121...
2 A
0980 XSL 3912-121...
2 A
0980 LSL 3x11-121...
Max. output current per
channel
0980 LSL 3x10-121...
0.5 A (power supplied via U
S
)
Short-circuit/overload
protected
yes/yes
Behavior in case of short
circuit or overload
disconnection with automatic power-on
0980 XSL 3912-121...
0980 LSL 3x11-121...
8
Number of digital outputs
0980 LSL 3x10-121...
4
Status indicator
yellow LED per output
Diagnostic indicator
red LED per channel
Table 42: IO-Link Master Ports configured as digital outputs
3
Max. 2.0 A per channel; max. 6.5 A in total for every port pair (X1/X2,
X3/X4, X5/X6, X7/X8); max. 9.0 A in total (with derating) for the whole
port group (X1 .. X8)
Manual EtherCAT®
Version 1.1 04/2021
143