56
Installation RSR20/RSR30
Release 06 07/2021
IEEE C37.90.1
Damped oscillation
DC Power line
AC Power line
Data line
+/- 2.5kV line/ground
+/- 1kV line/line
+/- 2.5kV line/ground
+/- 1kV line/line
+/- 2.5kV line/ground
+/- 1kV line/line
+/- 2.5kV line/ground
+/- 1kV line/line
+/- 2.5kV line/ground
+/- 1kV line/line
+/- 2.5kV line/ground
+/- 1kV line/line
IEEE C37.90
H.V. Impulse
DC Power line
AC Power line
+/- 5 kV line/ground
+/- 5 kV line/ground
+/- 5 kV line/ground
+/- 5 kV line/ground
IEEE C37.90
Electrical strength
DC Power line power supply
unit type C
Signal contact
500 VAC
a
2000 VAC
500 VAC
a
2000 VAC
a. Protective elements limit this voltage to 60 VDC (1 mA)
Environment
TYPE tests, test in
comp. with
Description
Certification C
Test level
Certification H
Test level
IEC 60068-2-1
Cold
-40 °C, 16 hours
-40 °C, 16 hours
IEC 60068-2-2
Dry heat
+85 °C, 16 hours
+85 °C, 16 hours
IEC 60068-2-30
Relative humidity
95 % (non-
condensed), 55 °C 4
cycles
95 % (non-
condensed), 55 °C 4
cycles
IEC 60068-2-6
Vibration, test Fc
2- 9 Hz with 3 mm
amplitude
1 g at 9 - 200 Hz
1.5 g at 200 - 500 Hz
2- 9 Hz with 3 mm
amplitude
1 g at 9 - 200 Hz
1.5 g at 200 - 500 Hz
IEC 60068-2-27
Shock, test Ea
15 g at 11 ms
15 g at 11 ms
IEC 60068-2-27
Shock
5 g at 30 ms
-
IEC 60068-2-64
Vibration
5 Hz - 150 Hz
broadband noise
a
a. During storage: 5.9 m/s2 (vertical) 3.9 m/s2 (horizontal), 5 h / axis
-
EMC emitted interference
Certification C
Certification H
EN 55022
Class A
Class A
FCC 47 CFR Part 15
Class A
Class A
German Lloyd
Classification and
Construction
Guidelines VI-7-3
Part 1 Ed.2003
Classification and
Construction
Guidelines VI-7-3
Part 1 Ed.2003
IEEE 1613:2009
EMI TYPE tests,
test in comp. with
Description
Certification C
Test level
Certification H
Test level