6.4 Configuration of the LioN-P PRO-
FINET I/O modules in STEP 7
57
Digital-I/O mode for Ch. B/Pin 2 (LioN-P 60 devices)
The type B IO-Link ports, ports 5- 8 on the LioN-P 60 devices, can be
parameterized as follows:
Figure 25: Digital I/O mode (LioN-P 60 devices)
Default setting:
Auxiliary Power Supply (IO-Link Type B)
Auxiliary Power (IO-Link Type B):
In this mode, Pin 2 and Pin 5 of the type B IO-Link ports, ports 5 - 8,
act as an auxiliary voltage output. The auxiliary voltage is fed from the
U
Aux
supply input. The auxiliary voltage output cannot be controlled.
Digital Output (DO):
In this mode, Ch. B/Pin 2 of the type B IO-Link ports, ports 5 - 8, can
be used as a digital output. The control bits are transferred by the
control unit to the device within the status/control module. A
"Surveillance-Timeout" can be parameterized for the outputs (tab
"Surveillance Timeout Configuration").