Configuration and startup
34
5.4 Configuration of the LioN-R
PROFINET I/O modules in STEP 7
Technical manual LioN-P/ -R PROFINET
Release 1.2 02/2016
The Surveillance Timeout parameter
This parameter is provided by the module types with digital outputs
(16DO, 8DI/DO).
The firmware of the modules allows you to define a delay time before the
monitoring of the output currents begins, known as the surveillance
timeout. You can define this for every individual output channel.
The delay time begins after the status of the output channel changes, i.e.
when this is activated (after a rising edge) or deactivated (after a falling
edge). After this time has elapsed, the monitoring of the output begins and
the diagnosis reports error statuses.
The value of the surveillance timeout is 0 to 255 ms. The standard value
is 80 ms. When the output channel is in the static state, i.e. the channel is
permanently switched on or off, the value is 100 ms.
5.4.5
Prioritized startup
Prioritized startup is not supported by LioN-P/-R modules. Do not select the
"Prioritized startup" field in the "Properties - Interface (X1)" window for this
reason.
Содержание 934 692-001
Страница 2: ...2 Technical manual LioN P R PROFINET Release 1 2 02 2016...
Страница 6: ...Content 6 Technical manual LioN P R PROFINET Release 1 2 02 2016...
Страница 10: ...About this manual 10 1 3 Version information Technical manual LioN P R PROFINET Release 1 2 02 2016...
Страница 26: ...Assembly and wiring 26 4 3 Port assignments Technical manual LioN P R PROFINET Release 1 2 02 2016...
Страница 62: ...Technical data 62 9 7 LEDs Technical manual LioN P R PROFINET Release 1 2 02 2016...
Страница 64: ...Declaration of conformity 64 Technical manual LioN P R PROFINET Release 1 2 02 2016...