Configuration and startup
Technical manual LioN-P/ -R PROFINET
Release 1.2 02/2016
5.4 Configuration of the LioN-R
PROFINET I/O modules in STEP 7
33
The Report Alarms parameter
With this parameter, you enable or disable the alarms of the device-
specific diagnostics via PROFINET.
The setting is available for all three different types of modules (16DI,
16DO, 8DI/8DO).
The Fail Safe parameter
This parameter is provided by the module types with digital outputs
(16DO, 8DI/DO).
The firmware of the modules provides a fail-safe function for the outputs.
During the configuration of the modules, you have the option to define the
status of the outputs after an interruption or a loss of communication.
The following options are available to you:
Set low
– deactivate the output channel (value = 0)
Set high
– activate the output channel (value = 1)
Hold last
– hold the last output status (value = 2)