Diagnostics processing
Technical manual LioN-P/ -R EtherNet/IP
Release 1.4 02/2016
9.4 Error in the actuator power supply
55
The error message is filtered by the "Surveillance-Timeout" parameter.
9.4
Error in the actuator power supply
The voltage value at the connections for the power supply of the actuators is
monitored globally and on the module level.
If the actuator power supply U
L
goes outside the voltage range of 18 to 30 V,
an error is reported. The U
L
indicator lights up red, and the actuator
undervoltage bit is set in the module information byte.
When output channels are activated, the voltage error is also displayed by
setting the relevant error bits of the M12 slots.
The error message is filtered by means of a fixed filter period of 300 ms.
9.5
Error in the system/sensor power supply
The voltage value for the system/sensor power supply is also monitored
globally. If the value goes outside the voltage range of 18 to 30 V, an error
message is created.
The U
S
indicator lights up red and the sensor undervoltage bit is set in the
module information byte.
Note
Every output channel that is active at the same time as the error occurs in
supply voltage U
L
is locked. This means that for correct operation, the
output channel must be reset by the controller when the status of the supply
voltage U
L
is normalized again.
We recommend deactivating all output channels with the controller as soon
as the undervoltage is detected. Otherwise, because it is locked, every
active output channel will report a diagnosis when the voltage value is
normalized again.
Содержание 934 691-001
Страница 2: ...2 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 6: ...Content 6 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 10: ...About this manual 10 1 3 Version information Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 16: ...System description 16 3 3 Product overview Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 47: ...QuickConnect Technical manual LioN P R EtherNet IP Release 1 4 02 2016 7 2 Activation 47...
Страница 48: ...QuickConnect 48 7 2 Activation Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 62: ...Technical data 62 10 7 LEDs Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 64: ...Declaration of conformity 64 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 68: ...Accessories 68 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...