Assembly and wiring
Technical manual LioN-P/ -R EtherNet/IP
Release 1.4 02/2016
4.3 Port assignments
25
4.3.4
Power supply with M12 power L-coded
Color coding: gray
Figure 6: Schematic diagram of the M12 L-coding (connector), port X03 (IN)
Figure 7: Schematic diagram of the M12 L-coding (socket), port X04 (OUT)
NOTE
Only use power supply units for the system/sensor and actuator supply that
correspond to PELV (Protective Extra Low Voltage) or SELV (Safety Extra
Low Voltage). Power supplies according to EN 61558-2-6 (transformers) or
EN 60950-1 (switching power supply units) fulfill these requirements.
Power supply
Pin
Signal
Function
1
V
s
(+24V)
Sensor/system power supply
2
GND_U
L
Ground/reference potential V
aux
3
GND_V
S
Ground/reference potential V
s
4
U
L
(+24V)
Auxiliary supply
(electrically isolated)
PE (5)
PE
Functional ground
Table 6:
Assignment of X03, X04
Содержание 934 691-001
Страница 2: ...2 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 6: ...Content 6 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 10: ...About this manual 10 1 3 Version information Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 16: ...System description 16 3 3 Product overview Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 47: ...QuickConnect Technical manual LioN P R EtherNet IP Release 1 4 02 2016 7 2 Activation 47...
Страница 48: ...QuickConnect 48 7 2 Activation Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 62: ...Technical data 62 10 7 LEDs Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 64: ...Declaration of conformity 64 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 68: ...Accessories 68 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...