5 Starting operation

5.1

Downloading and installing the EDS file

An EDS file is required for the configuration of a module in the controller. 
Each of the 3 module variants requires its own EDS file. You have the option 
of downloading the EDS file from our website or asking our support team to 
send it to you. The address of the website is:

http://www.beldensolutions.com/de/Service/Downloadcenter/

Software_Lumberg

The EDS files are grouped together in an archive file with the name 

LioN-P 

ETHERNET-IP EDS V3.9

. Download this file and unpack it.

The archive contains the following EDS files:

EDS-V3.9-LumbergAutomation-0980ESL811-yyyymmdd.eds

EDS-V3.9-LumbergAutomation-0980ESL812-yyyymmdd.eds

EDS-V3.9-LumbergAutomation-0980ESL813-yyyymmdd.eds

EDS-V3.9-LumbergAutomation-0980ESL311-xxx-yyyymmdd.eds

EDS-V3.9-LumbergAutomation-0980ESL312-xxx-yyyymmdd.eds

EDS-V3.9-LumbergAutomation-0980ESL313-xxx-yyyymmdd.eds

EDS-V3.9-LumbergAutomation-0980ESL391-xxx-yyyymmdd.eds

EDS-V3.9-LumbergAutomation-0980ESL392-xxx-yyyymmdd.eds

EDS-V3.9-LumbergAutomation-0980ESL393-xxx-yyyymmdd.eds

yyyymmdd

 stands for the date on which the file was issued.

Install the EDS file for the module variant used with the aid of the hardware 
or network configuration tool of your controller manufacturer. After the 
installation, the modules are available in the hardware catalogs as a "General 
Purpose Discrete I/O" device.

Содержание 934 691-001

Страница 1: ...support automation belden com Technical manual LioN P EtherNet IP with QuickConnect 0980 ESL 311 xxx 0980 ESL 313 xxx 0980 ESL 391 xxx 0980 ESL 393 xxx LioN R EtherNet IP with QuickConnect 0980 ESL 81...

Страница 2: ...2 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...

Страница 3: ...ial product features 13 3 3 Product overview 14 4 Assembly and wiring 17 4 1 General information 17 4 2 Outer dimensions 19 4 2 1 Module 0980 ESL 813 EIP 8DI 8DO M12 R 19 4 2 2 Module 0980 ESL 313 111...

Страница 4: ...45 7 1 How it works 45 7 2 Activation 45 7 2 1 Configuration assembly instance 105 46 7 2 2 EtherNet IP object TCP IP object 46 8 Bit assignment 49 8 1 16DI module 49 8 1 1 Assembly instance ID 101 in...

Страница 5: ...54 9 3 Overload of output drivers 54 9 4 Error in the actuator power supply 55 9 5 Error in the system sensor power supply 55 10 Technical data 57 10 1 General 57 10 2 Bus system 57 10 3 Power supply...

Страница 6: ...Content 6 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...

Страница 7: ...used in this manual are used exclusively to explain how to operate and apply the LioN P and LioN R P modules with EtherNet IP interface Please contact us if you have any detailed questions on install...

Страница 8: ...or substantial damage to property will occur if the required safety measures are not taken WARNING Means that death serious physical injury or substantial damage to property can occur if the required...

Страница 9: ...information Index Created Changed Changed Version number Version 1 0 Version 1 1 Version 1 2 Date March 2013 May 2013 Aug 2014 Name department Knipp PM Knipp PM Knipp PM Version number Version 1 3 Ve...

Страница 10: ...About this manual 10 1 3 Version information Technical manual LioN P R EtherNet IP Release 1 4 02 2016...

Страница 11: ...d in the industrial sector The industrial environment is distinguished by the fact that the consumer is not connected directly to the public low voltage network Additional measures are required for us...

Страница 12: ...are based on the requirement profiles described by ZVEI VDMA or equivalent organizations Only electricians who are familiar with the content of this manual are authorized to install and maintain the...

Страница 13: ...dule electronics from environmental effects and allows the device to be used in a wide temperature range Despite the sturdy construction the modules have compact dimensions and a low weight They are e...

Страница 14: ...e the behavior of every single output channel in the case of an interruption or a loss of communication Integrated web server The network parameters such as IP address subnet mask and gateway can be a...

Страница 15: ...0980 ESL 812 EIP 16DO M12 R SAP number 934 691 002 0980 ESL 312 111 single protocol SAP number 934 880 002 0980 ESL 312 121 single protocol SAP number 934 839 002 0980 ESL 392 111 multiprotocol SAP nu...

Страница 16: ...System description 16 3 3 Product overview Technical manual LioN P R EtherNet IP Release 1 4 02 2016...

Страница 17: ...ocket and a distance of 196 8 to 198 3 mm for LioN P modules with M12 power L coded Note The modules have a ground connection with an M4 thread for the conduction of interference currents and the EMC...

Страница 18: ...ries Note For UL application Only approved for interior use Please note the maximum elevation of 2000 meters Approved up to a maximum soiling level of 2 WARNING Terminals housings field wired terminal...

Страница 19: ...Assembly and wiring Technical manual LioN P R EtherNet IP Release 1 4 02 2016 4 2 Outer dimensions 19 4 2 Outer dimensions 4 2 1 Module 0980 ESL 813 EIP 8DI 8DO M12 R...

Страница 20: ...Assembly and wiring 20 4 2 Outer dimensions Technical manual LioN P R EtherNet IP Release 1 4 02 2016 4 2 2 Module 0980 ESL 313 111...

Страница 21: ...Assembly and wiring Technical manual LioN P R EtherNet IP Release 1 4 02 2016 4 2 Outer dimensions 21 4 2 3 Module 0980 ESL 313 121...

Страница 22: ...1 Ethernet IP ports Design M12 socket 4 pin D coded Color coding green Figure 1 Schematic drawing ports X01 X02 4 3 2 Ports for the power supply Design MINI 7 8 connector socket 4 pin Color coding gr...

Страница 23: ...ensors US 3 0 V DC System sensors US 4 0 V DC Actuator UL Table 4 Assignment of ports X03 X04 NOTE Only use power supply units for the system sensor and actuator supply that correspond to PELV Protect...

Страница 24: ...1 0980 ESL 802 0980 ESL 803 Power supply X03 X04 1 see note Actuator GND 0V 2 GND 0V System sensors GND 0V 3 FE Ground Functional ground 4 24 V System sensors US 24 V 5 see note Actuator VL 24 V Table...

Страница 25: ...supply units for the system sensor and actuator supply that correspond to PELV Protective Extra Low Voltage or SELV Safety Extra Low Voltage Power supplies according to EN 61558 2 6 transformers or EN...

Страница 26: ...Protective Extra Low Voltage or SELV Safety Extra Low Voltage Power supplies according to EN 61558 2 6 transformers or EN 60950 1 switching power supply units fulfill these requirements Port Pin Funct...

Страница 27: ...unpack it The archive contains the following EDS files EDS V3 9 LumbergAutomation 0980ESL811 yyyymmdd eds EDS V3 9 LumbergAutomation 0980ESL812 yyyymmdd eds EDS V3 9 LumbergAutomation 0980ESL813 yyyy...

Страница 28: ...tings The devices support the DHCP and BOOTP protocols for receiving the required network parameters such as IP address and subnet mask The factory settings of the static network parameters are IP add...

Страница 29: ...used Rotary switch setting Function 000 state on delivery In the state on delivery the DHCP and BOOTP functions are activated The network parameters are initially requested via DHCP requests If this i...

Страница 30: ...Connection type Diagnostics Instance ID Length Input Only Yes Output 193 0 byte Input 101 4 byte Input Only No Output 193 0 byte Input 102 3 byte Listen Only Yes Output 192 0 byte Input 101 4 byte Lis...

Страница 31: ...el Listen Only Yes Output 192 0 byte Input 101 7 byte Listen Only No Output 192 0 byte Input 102 3 byte Connection type Diagnostics Instance ID Length Exclusive Owner Yes Output 100 1 byte Input 101 6...

Страница 32: ...of the surveillance timeout is 0 to 255 ms The standard value is 80 ms When the output channel is in the static state i e the channel is permanently switched on or off the value is 100 ms MSB LSB 15 1...

Страница 33: ...ng a control system from another provider please consider the related documentation Install the EDS files of the modules in RSLogix5000 with the EDS hardware installation tool under the Tools menu Sel...

Страница 34: ...anual LioN P R EtherNet IP Release 1 4 02 2016 Go to the I O Configuration section in the Controller Organizer and right click on Ethernet Select the New Module menu item The following selection windo...

Страница 35: ...ick the Change button and change the setting for the module revision electronic keying and connection type Select the connection type This specifies which process and diagnostic data the module provid...

Страница 36: ...1 4 02 2016 Change to the Controller Tags section in Controller Organizer The controller tags for the configuration parameters contain the name of the module followed by a C The surveillance timeout a...

Страница 37: ...mum 2 ms LioN P Sender to target device O T connection parameters Real time transfer format Heartbeat Connection type POINT2POINT Assembly instance ID 193 Data type USINT Data size 1 byte Data length...

Страница 38: ...ort type Exclusive Owner Trigger mode Cyclic Requested packet interval RPI Minimum 5 ms LioN R Minimum 2 ms LioN P Sender to target device O T connection parameters Real time transfer format 32 bit ru...

Страница 39: ...e the option to call up the websites saved on it by entering the address in a web browser To do this replace the placeholder IP Adresse with the IP address of the relevant module 6 1 The Home page The...

Страница 40: ...and writable Gateway address readable and writable Start configuration Fix The module uses the IP settings defined by the above parameters BOOTP The module receives the IP settings via a BOOTP server...

Страница 41: ...ta Consumed Input data Produced with diagnosis Status of the LAN ports Duplex mode full duplex half duplex Transmission rate 10 MBit 100 MBit Network address MAC address Size and data direction of the...

Страница 42: ...e Contact page Technical manual LioN P R EtherNet IP Release 1 4 02 2016 6 4 The Contact page The address of the contact page is http IP Adresse contact htm This page provides information on the conta...

Страница 43: ...erver The web server provides the data in standardized JSON format The data is accessed via the website The relevant address is http IP Adresse data jsn In higher programming languages the process and...

Страница 44: ...diagno stic data Technical manual LioN P R EtherNet IP Release 1 4 02 2016 The response has the following object structure Consumed Array a b contains the output data of the module Produced Array a b...

Страница 45: ...nd DHCP BOOTP are not supported Please note that no automatic check is performed for IP addresses that are assigned more than once in the same network When QuickConnect is activated the following para...

Страница 46: ...r Organizer select the Controller Tags section and set the QuickConnectEn bit to the value 1 7 2 2 EtherNet IP object TCP IP object Enter a message command from the command list and open the related c...

Страница 47: ...QuickConnect Technical manual LioN P R EtherNet IP Release 1 4 02 2016 7 2 Activation 47...

Страница 48: ...QuickConnect 48 7 2 Activation Technical manual LioN P R EtherNet IP Release 1 4 02 2016...

Страница 49: ...ata without diagnosis 8 1 3 Key X1 A X8 A Input status channel A contact pin 4 of slots X1 to X8 X1 B X8 B Input status channel B contact pin 2 of slots X1 to X8 MI LVS Module information byte undervo...

Страница 50: ...3 Bit 2 Bit 1 Bit 0 Byte 0 X4 B X4 A X3 B X3 A X2 B X2 A X1 B X1 A Byte 1 X8 B X8 A X7 B X7 A X6 B X6 A X5 B X5 A Byte 2 MI IME 0 0 0 MI SCA 0 MI LVA MI LVS Byte 3 0 0 0 0 0 0 0 0 Byte 4 0 0 0 0 0 0 0...

Страница 51: ...NPUT Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte 0 X4 B X4 A X3 B X3 A X2 B X2 A X1 B X1 A Byte 1 X8 B X8 A X7 B X7 A X6 B X6 A X5 B X5 A Byte 2 MI IME 0 0 0 MI SCA MI SCS MI LVA MI LVS Byte...

Страница 52: ...s channel B contact pin 2 of slots X5 to X8 MI LVS Module information byte undervoltage for system sensor power supply MI LVA Module information byte actuator undervoltage MI SCS Module information by...

Страница 53: ...of the module The value of this parameter can range from 0 to 255 ms the factory setting is 80 ms Target value Actual value Comment Active Active OK no diagnosis Off Off OK no diagnosis Active Off Sho...

Страница 54: ...et light up red and the relevant error bit for the sensor short circuit is set in the diagnosis bytes The error message is filtered by the Surveillance Timeout parameter 9 3 Overload of output drivers...

Страница 55: ...The error message is filtered by means of a fixed filter period of 300 ms 9 5 Error in the system sensor power supply The voltage value for the system sensor power supply is also monitored globally If...

Страница 56: ...therNet IP Release 1 4 02 2016 The error message has no effect on the outputs and is not filtered but is reported immediately Caution It must definitely be ensured that the supply voltage measured at...

Страница 57: ...s Torques M6 fixing screws M4 ground connection M12 connector 1 0 Nm 1 0 Nm 0 5 Nm Table 29 General information Protocol EtherNet IP EDS files EDS V3 9 LumbergAutomation 0980ESL811 yyyymmdd eds EDS V3...

Страница 58: ...I 7 8P MP 39200 0980 ESL 392 111 16DO 7 8P MP 39300 0980 ESL 393 111 8DI8DO 7 8P MP 39102 0980 ESL 391 121 16DI M12P MP 39202 0980 ESL 392 121 16DO M12P MP 39302 0980 ESL 393 121 8DI8DO M12P MP Suppor...

Страница 59: ...larity protection Yes Operational indicator UL LED green 18 V UL 30 V LED red UL 18 V or UL 30 V Table 32 Information on the power supply for the actuators Input connection Type 3 as per IEC 61131 2 N...

Страница 60: ...ls 0 with 16 DI 16 with 16DO 8 with 8DI 8DO Channel type Normally open p switching Status indicator LED yellow per channel A LED white per channel B Diagnosis indicator LED red per channel Port M12 so...

Страница 61: ...ubscriber No link no data exchange MS Green Device ready for operation Flashing green Device ready but not configured Red Serious error that cannot be resolved Flashing red Minor error that can be res...

Страница 62: ...Technical data 62 10 7 LEDs Technical manual LioN P R EtherNet IP Release 1 4 02 2016...

Страница 63: ...Declaration of conformity Technical manual LioN P R EtherNet IP Release 1 4 02 2016 63 11 Declaration of conformity...

Страница 64: ...Declaration of conformity 64 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...

Страница 65: ...ector at both ends straight 4 pin D coded and RJ45 connector 26AWG PUR halogen free with water blue casing multi wire shielded 2 twisted wire pairs 0985 706 100 M Connection cable for PROFINET with M1...

Страница 66: ...cable plug RS and socket RK straight 4 pin 18AWG TPE conductor IEC color coded RSRK 40 602 M MINI 7 8 connection cable both ends with cable plug RS and socket RK straight 4 pin 18AWG PUR conductor IEC...

Страница 67: ...ories Technical manual LioN P R EtherNet IP Release 1 4 02 2016 67 Item number Description RKV Cover for unused MINI 7 8 device sockets RSV Cover for unused MINI 7 8 device plugs Table 40 Other access...

Страница 68: ...Accessories 68 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...

Отзывы: