Diagnostics processing
54
9.2 Voltage error at the M12 slots
(sensor short-circuit)
Technical manual LioN-P/ -R EtherNet/IP
Release 1.4 02/2016
The filter is used to avoid premature error messages when a capacitive load
is activated or an inductive load is deactivated, and during other voltage
peaks when a status changes.
When a channel is in the static state – that is, when it is permanently
activated or deactivated – the controller uses a fixed specified duration of 100
ms for filtering the error message.
9.2
Voltage error at the M12 slots (sensor short-
circuit)
At every M12 input socket of the modules, pin 1 supplies a monitored sensor
voltage V
S
.
In the case of a sensor short-circuit, a voltage error is reported. Both channel
indicators of the M12 input socket light up red, and the relevant error bit for
the sensor short-circuit is set in the diagnosis bytes.
The error message is filtered by the "Surveillance-Timeout" parameter.
9.3
Overload of output drivers
The output drivers of the modules with output functions (variants 16DO and
8DI/8DO) report an error when they detect an overload. This error is reported
by setting the relevant channel error bits in the diagnosis bytes.
If there is an overload, the status indicator of the active output channel lights
up red. If both output channels of an M12 slot are active during an overload,
both status indicators light up red.
Note
If both output channels of an M12 slot are activated when a channel error
occurs, the controller locks both channels, even if only one channel is
affected by the error. If only one channel is activated, the controller only
locks this one. Locked channels are deactivated and remain in the
Off
state
if you do not reset them using the controller.
Содержание 934 691-001
Страница 2: ...2 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 6: ...Content 6 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 10: ...About this manual 10 1 3 Version information Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 16: ...System description 16 3 3 Product overview Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 47: ...QuickConnect Technical manual LioN P R EtherNet IP Release 1 4 02 2016 7 2 Activation 47...
Страница 48: ...QuickConnect 48 7 2 Activation Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 62: ...Technical data 62 10 7 LEDs Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 64: ...Declaration of conformity 64 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Страница 68: ...Accessories 68 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...