Connection of the sensors
METPOINT® BDL
21
11 Connection of the sensors
As regards consumption and dew point sensors, there is the possibility to provide the measured values as an
analog current signal 4 – 20 mA for further processing. In the connection diagrams, the collection of the
current signal for an external PLC/central control system or for an external display is explained.
SD21
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Connecting plug
+U
v
Not used
+
I
OUT
Not used
Not used
Connecting lead
4025252 (5 m)
Brown
White
SD23
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Connecting plug
+U
v
Not used
Not used
+
I
OUT
-U
v
GND
Connecting lead
4025253 (5 m)
Brown
White
Blue
Black
SP21/SP61
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Connecting plug
+U
v
Not used
+
I
OUT
Not used
Not used
Connecting lead
4025252 (5 m)
Brown
Blue
SP22/SP62
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Connecting plug
+U
v
GND
-
U
v
-
U
OUT
Not used
Connecting lead
Upon request
Brown
Black
Blue
White
FS109/FS211/DP109
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Connecting plug
SDI
-
U
v
+
U
v
+I (500 µA)
Not used
Connecting lead
4014064 (5 m)
4014065 (10 m)
Brown
White
Blue
Black
Grey
The following connection diagrams apply from XA.1 to XC.4!
SD/DP series = dew point sensors
FS series = consumption sensors
SP series = pressure transducer
Содержание METPOINT BDL portable
Страница 1: ...EN English Instructions for installation and operation Graphic display recorder METPOINT BDL 10 045 ...
Страница 12: ...Technical data BDL 12 METPOINT BDL 8 3 Housing dimensions ...
Страница 31: ...Connection of the sensors METPOINT BDL 31 11 8 Assignment RS485 Sensor with an RS485 interface ...
Страница 88: ...Operation BDL 88 METPOINT BDL Main menu Graphics ...
Страница 105: ...METPOINT BDL 105 ...
Страница 106: ...106 METPOINT BDL ...
Страница 107: ...METPOINT BDL 107 ...