9
Heatless Desiccant Dryers
|
Instruction Manual
Connecting the pre-filter to the dryer
• 4 SCFM – 35 SCFM, Utilize O-ring and bolts supplied to
assemble filter as per figure 3.1.
• Fit 5/32” (4mm) tubing to filter and dryer’s built-in drain
valve inlet.
• Pipe away condensate with 5/32” (4mm) tubing from the
dryer’s drain outlet. Ensure condensate is drained into an
oil/water separator.
• Fit any further filtration or ancillary equipment.
• Drain kits supplied with dryer and comprise of the
following: Swivel elbow adapter and 5/32” (4mm) tubing.
It is recommended that a bypass line including filter is
installed, as per figure 3.13
17. Exhaust silencer
18. Purge plug
19. Purge plug fixing screw
20. Pre-filter
21. Power cord
22. Down tube
1
2
Figure 3.1: Connecting pre-filter
Mechanical Installation
Section 3:
Mechanical Installation
1. Inlet
2. Outlet
Figure 3.2: Connecting filter drain
All tubing should be secured up to the point of drain to
prevent whipping during discharge.