5�7 Wiring
5�7�1 Before performing any electrical
work, read these regulations
1. All wiring must comply with local and national
electrical codes, regulations and must be
installed by a licensed electrician.
2. All electrical connections must be made
according to the Electrical Connection Diagram
located on the panels of the indoor and outdoor
units.
3. If there is a serious safety issue with the power
supply, stop work immediately. Explain your
reasoning to the client, and refuse to install the
unit until the safety issue is properly resolved.
4. Power voltage should be within 90-110% of
rated voltage. Insufficient power supply can
cause malfunction, electrical shock, or fire.
5. If connecting power to fixed wiring, a surge
protector and main power switch should be
installed.
6. If connecting power to fixed wiring, a switch
or circuit breaker that disconnects all poles
and has a contact separation of at least 1/8in
(3mm) must be incorporated in the fixed wiring.
The qualified technician must use an approved
circuit breaker or switch.
7. Only connect the unit to an individual branch
circuit outlet. Do not connect another appliance
to that outlet.
8. Make sure to properly ground the air conditioner.
9. Every wire must be firmly connected. Loose
wiring can cause the terminal to overheat,
resulting in product malfunction and possible
fire.
10. Do not let wires touch or rest against refrig-
erant tubing, the compressor, or any moving
parts within the unit.
5 Installation
11. If the unit has an auxiliary electric heater, it
must be installed at least 1 meter (40in) away
from any combustible materials.
12. To avoid getting an electric shock, never touch
the electrical components soon after the pow-
er supply has been turned off. After turning off
the power, always wait 10 minutes or more
before you touch the electrical components.
13. Make sure that you do not cross your electrical
wiring with your signal wiring. This may cause
distortion and interference.
14. The unit must be connected to the main out-
let. Normally, the power supply must have a
impedance of 32 ohms.
15. No other equipment should be connected to
the same power circuit.
16. Connect the outdoor wires before connecting
the indoor wires.
A
WARNING!
Before performing
any electrical or wiring work, turn
off the Main power to the system.
C
When the maximum current of
the air conditioner is more than
16A, an air switch or leakage
protection switch with protective
device shall be used (purchased
seperately). When the maximum
current of the air conditioner
is less than 16A, the power
cord of air conditioner shall be
equipped with plug (purchased
seperately). The North American
market is wired according to
NEC and CEC requirements.