8.2 Commissioning tasks
Illustration
Description / explanation
E
1. Supply the
BEKOMAT
®
with voltage.
E
2. Slowly charge the system section with pressure. To do
this, slowly open the shut-off valve
[E]
.
9. Operation
As soon as the
BEKOMAT
®
is supplied with voltage, a self-test starts automatically, during which all internal
components necessary for the proper functioning of the
BEKOMAT
®
are checked.
If the self-test is positive, the
BEKOMAT
®
goes into normal operation.
0
For acoustic signalling, the solenoid valve cycles twice.
If the self-test is negative, the
BEKOMAT
®
goes into fail-safe operation.
0
For acoustic signalling, the solenoid valve cycles 20 times.
The LED signalling of the various operating states can be seen in the following table.
9.1 Operating states
Illustration
Description / explanation
Disconnected
•
All LEDs are off
Switch on / power-on self-test
• All LEDs light up for 1 second
BEKOMAT
®
13, 13 CO, 13 CO PN25, 13 CO PN40
Original installation and operation manual