Maintenance, troubleshooting, spare parts and dismantling
38
BEKOBLIZZ® LC 12-355
Failure during the
condensate discharge.
Please read the separate BEKOMAT installation and operating instructions.
Water in the line.
The
chiller
does not start – see the corresponding point.
If installed - untreated air flows through the bypass unit – close the bypass.
The
chiller
does not drain condensate – see the corresponding point.
Dew point too high – see the corresponding point.
If installed :
The HPS high-pressure
switch has triggered.
Check which of the following reasons is responsible for the triggering:
1.
The ambient temperature is too high or the room ventilation insufficient – ensure sufficient
ventilation (air-cooled).
2.
The condenser is dirty – please clean it (air-cooled).
3.
The condenser fan does not work – see the corresponding point (air-cooled).
4.
The cooling water is too hot – re-establish the nominal conditions (water-cooled).
5.
The cooling-water flow is insufficient – re-establish the nominal conditions (water-cooled).
Reset the pressure switch by pressing the button on the controller itself – check the proper
functioning of the
chiller
.
The HPS pressure switch is defective – contact a BEKO service technician for the replacement.
If
installed:
the LPS low-pressure
switch was triggered.
There is a leak in the refrigeration cycle – please contact a BEKO service technician.
The pressure switch is automatically reset as soon as the normal conditions are re-established –
check the
chiller
for proper functioning.
If
installed:
the TS
safety
temperature switch was
triggered.
Check which of the following reasons is responsible for the triggering:
1.
Excess thermal load – re-establish the standard operating conditions.
2.
The inlet air is too hot – re-establish the nominal conditions.
3.
The ambient temperature is too high or the room ventilation insufficient – ensure sufficient
ventilation.
4.
The condenser unit is dirty – please clean it.
5.
The fan does not work – see the corresponding point.
6.
The hot-gas bypass valve needs to be re-adjusted – contact a specialist for refrigerating plants to
have the nominal calibration re-established.
7.
The cooling-water temperature is too low – re-establish the nominal conditions (water-cooled).
8.
The adjusting valve for the cooling-water flow needs to be re-adjusted – contact a specialist to
have the nominal calibration re-established (water-cooled).
9.
There is a leak in the refrigeration cycle – please contact a BEKO service technician.
Reset the temperature switch by manually pushing the button on the temperature switch – check
the perfect functioning of the
chiller
.
The TS temperature switch is defective – replace it.
DMC15 –
The first and the last led
of the display are flashing
syncronous.
Verify the electric wiring of T1 DewPoint probe.
The T1 DewPoint probe is faulty - replace it.
The DMC15 electronic control unit is faulty - replace it.
DMC15 –
The
yellow led is
flashing (LC 12-35)
Verify the electric wiring of T2 fan control probe.
The T2 fan control probe is faulty - replace it.
The DMC15 electronic control unit is faulty - replace it.
DMC15 –
The first led of the display
is flashing.
DewPoint too low - see specific point.
The T1 DewPoint probe is faulty - replace it.
The DMC15 electronic control unit is faulty - replace it.
DMC15 –
The last led of the display
is flashing.
DewPoint too high - see specific point.
The T1 DewPoint probe is faulty - replace it.
The DMC15 electronic control unit is faulty - replace it.
The
DMC18
LED
is on.
When the
LED flashes: one or more service warnings/alarms are active. The display
shows the dew point temperature and the active service warnings/alarms.
The service warnings are indicated by the following messages:
1.
: PF – Failure temperature probe T1 (dew point) – check the electric cabling and/or
replace the probe.
2.
: Hdp – Dew point too high (higher than the adjusted alarm value) – see the
corresponding section.
3.
: Ldp – Dew point too low (lower than the adjusted alarm value) – see the
corresponding section.
4.
: drA – The Bekomat BM-IF condensate drain does not work properly - see the
corresponding section.
5.
: SrV - Service – maintenance notification time expired (parameter SrV) – carry out
the scheduled maintenance and reset the hour meter.
NOTE: SrV Service (service time expired) needs to be reset manually (press the
button and keep it pressed for at least 20 seconds).
Содержание Bekoblizz LC 12-355
Страница 22: ...Technical data 22 BEKOBLIZZ LC 12 355 10 Technical data 10 1 Technical data BEKOBLIZZ LC 12 35 1 230 50 60 ...
Страница 23: ...Technical data BEKOBLIZZ LC 12 355 23 10 2 Technical data BEKOBLIZZ LC 55 355 1 230 50 ...
Страница 24: ...Technical data 24 BEKOBLIZZ LC 12 355 10 3 Technical data BEKOBLIZZ LC 12 150 1 115 60 ...
Страница 25: ...Technical data BEKOBLIZZ LC 12 355 25 10 4 Technical data BEKOBLIZZ LC 55 355 1 230 60 ...
Страница 40: ...Maintenance troubleshooting spare parts and dismantling 40 BEKOBLIZZ LC 12 355 ...
Страница 41: ...Maintenance troubleshooting spare parts and dismantling BEKOBLIZZ LC 12 355 41 ...
Страница 44: ...Appendices 44 BEKOBLIZZ LC 12 355 13 1 2 Chiller dimensions BEKOBLIZZ LC 55 ...
Страница 45: ...Appendices BEKOBLIZZ LC 12 355 45 13 1 3 Chiller dimensions BEKOBLIZZ LC 90 115 ...
Страница 46: ...Appendices 46 BEKOBLIZZ LC 12 355 13 1 4 Chiller dimensions BEKOBLIZZ LC 150 240 ...
Страница 47: ...Appendices BEKOBLIZZ LC 12 355 47 13 1 5 Chiller dimensions BEKOBLIZZ LC 355 ...
Страница 49: ...Appendices BEKOBLIZZ LC 12 355 49 13 2 2 Exploded diagram BEKOBLIZZ LC 12 35 ...
Страница 50: ...Appendices 50 BEKOBLIZZ LC 12 355 13 2 3 Exploded diagram BEKOBLIZZ LC 55 ...
Страница 51: ...Appendices BEKOBLIZZ LC 12 355 51 13 2 4 Exploded diagram BEKOBLIZZ LC 90 115 ...
Страница 52: ...Appendices 52 BEKOBLIZZ LC 12 355 13 2 5 Exploded diagram BEKOBLIZZ LC 150 240 ...
Страница 53: ...Appendices BEKOBLIZZ LC 12 355 53 13 2 6 Exploded diagram BEKOBLIZZ LC 355 ...
Страница 60: ...Appendices 60 BEKOBLIZZ LC 12 355 ...
Страница 61: ...EC Declaration of Conformity BEKOBLIZZ LC 12 355 61 14 EC Declaration of Conformity ...
Страница 62: ...EC Declaration of Conformity 62 BEKOBLIZZ LC 12 355 ...