Technical description
30
BEKOBLIZZ® LC 12-355
11.16 DMC 15 electronics (control unit compressed-air chiller) – LC 12-35
DMC15
P
Q
S
0
0
36
DISPLAY
Set
ON
sec - min
ON
Led – Power ON
Led - Drain ON
Led – Condenser fan ON
Set
Button – Setup menu access
Button – Increase / Drain test (Not used)
The DMC15 displays DewPoint temperature and controls the condenser fan activation.
11.16.1 Switching the chiller on
Power the chiller and switch it on using the ON-OFF switch (pos.1 Section 11.1).
During normal operation led
ON
is ON and the display shows the DewPoint temperature by means of two coloured
areas (green and red) above a 10 Led display :
Green area - operating conditions ensuring an optimal DewPoint;
Red area - DewPoint too high, the chiller is operating with high thermal load (high inlet air temperature, high ambient
temperature, etc.). Compressed air treatment may be improper.
Led
shows that condensate drain solenoid valve is ON (Not used).
Led
shows that condenser fan is ON
The condensate drain test is always active using the button
(Not used).
11.16.2 Switching the chiller off
Switch the device off via the ON-OFF switch (pos. 1 Section 11.1).
11.16.3 Indication of a service warning/service alarm
A service warning/alarm is an exceptional event and requires the attention of the operator/service technician. The
chiller will not be stopped.
Service warnings/alarms are automatically reset as soon as the problem has been eliminated.
NOTE: the operator/service technician must check the chiller and eliminate the problem that led to the
activation of the service warning.
Service Warning / Alarm
Description
Display 1st (left) and 10th (right) led are flashing
Failure T1 (DewPoint) temperature probe.
Led
is flashing
Failure T2 (fan control) temperature probe.
NOTE : fan is forced always ON.
Display 10th (right) led is flashing
DewPoint too high
Display 1st (left) led is flashing
DewPoint too low
(lower than -1°C / 30°F).
Содержание Bekoblizz LC 12-355
Страница 22: ...Technical data 22 BEKOBLIZZ LC 12 355 10 Technical data 10 1 Technical data BEKOBLIZZ LC 12 35 1 230 50 60 ...
Страница 23: ...Technical data BEKOBLIZZ LC 12 355 23 10 2 Technical data BEKOBLIZZ LC 55 355 1 230 50 ...
Страница 24: ...Technical data 24 BEKOBLIZZ LC 12 355 10 3 Technical data BEKOBLIZZ LC 12 150 1 115 60 ...
Страница 25: ...Technical data BEKOBLIZZ LC 12 355 25 10 4 Technical data BEKOBLIZZ LC 55 355 1 230 60 ...
Страница 40: ...Maintenance troubleshooting spare parts and dismantling 40 BEKOBLIZZ LC 12 355 ...
Страница 41: ...Maintenance troubleshooting spare parts and dismantling BEKOBLIZZ LC 12 355 41 ...
Страница 44: ...Appendices 44 BEKOBLIZZ LC 12 355 13 1 2 Chiller dimensions BEKOBLIZZ LC 55 ...
Страница 45: ...Appendices BEKOBLIZZ LC 12 355 45 13 1 3 Chiller dimensions BEKOBLIZZ LC 90 115 ...
Страница 46: ...Appendices 46 BEKOBLIZZ LC 12 355 13 1 4 Chiller dimensions BEKOBLIZZ LC 150 240 ...
Страница 47: ...Appendices BEKOBLIZZ LC 12 355 47 13 1 5 Chiller dimensions BEKOBLIZZ LC 355 ...
Страница 49: ...Appendices BEKOBLIZZ LC 12 355 49 13 2 2 Exploded diagram BEKOBLIZZ LC 12 35 ...
Страница 50: ...Appendices 50 BEKOBLIZZ LC 12 355 13 2 3 Exploded diagram BEKOBLIZZ LC 55 ...
Страница 51: ...Appendices BEKOBLIZZ LC 12 355 51 13 2 4 Exploded diagram BEKOBLIZZ LC 90 115 ...
Страница 52: ...Appendices 52 BEKOBLIZZ LC 12 355 13 2 5 Exploded diagram BEKOBLIZZ LC 150 240 ...
Страница 53: ...Appendices BEKOBLIZZ LC 12 355 53 13 2 6 Exploded diagram BEKOBLIZZ LC 355 ...
Страница 60: ...Appendices 60 BEKOBLIZZ LC 12 355 ...
Страница 61: ...EC Declaration of Conformity BEKOBLIZZ LC 12 355 61 14 EC Declaration of Conformity ...
Страница 62: ...EC Declaration of Conformity 62 BEKOBLIZZ LC 12 355 ...