29
Fig 12 Control of valve in a process area.
The required instrument configurations for this
example are shown below.
Function
Display
Setting
Access code
CodE
0000
Function
FunCtion
ELAP5E
Input A
inPut-A
ContACt
Input b
inPut-b
ContaCt
De-bounce (both inputs)
dEbounCE
dEFAuLt
Display 2
di5P-2
5td
Start stop
5tAr5toP
ControL 2
Units
unit5
12 : 00 : 00
Set time
5Et t
00 : 05 : 00
Timer repeat cycle
CYCLE5
Enable repeat cycle
EnbL
on
Cycle count
cycl cnt
01
Reset delay
r5t dela
0000.05
Access set time from
AC5Et - t
oFF
display mode.
Direction of count
uP or dn
dn
Power failure
p-fail
idle
Local total reset
rE5Et
.
EnbL
on
Local grand total reset
CLr Gtot
oFF
External reset
e r5et
fa5t
Enable control output 1
EnbL
on
Control output 1 on at
oP1 on
run
Control output 1 off at
oP1 oFF
n run
Control output 1 delay
oP1 dELA
00000
Enable control output 2
EnbL
on
Control output 2 on at
oP2 on
done
Control output 2 off at
oP2 oFF
n done
Control output 2 delay
oP2 dELA
00005
Enable status output
EnbL
on
Status output on at
5tat on
re5et
Status output off at
5tat oFF
n re5et
Status
s
output delay
5tatdELA
00000
In this example local total reset
rE5Et . EnbL
is
on
.
This enables the Timer to be reset when power is
first connected by operating the
*
and
&
down
button simultaneously for more than 3 seconds.