19
5.5.8
Lower display:
di5P-2
The configuration options for the lower display vary
depending upon whether the repeat timer function
cycle5
is enabled.
CYCLE5
disabled
When the lower display is enabled it shows the
set time
5ET t
CYCLE5
enabled
When the lower display is enabled it shows the
total number of repeat cycles requested together
with the number of cycles performed. During the
delay time between cycles the display shows the
time until the next cycle starts.
Menu options allow each part of the cycle to be
briefly identified at the start of each part, or
periodically throughout the cycle.
To check or change the configuration of the lower
display select
di5P-2
from the configuration menu
and press
(
which will reveal the existing setting
which can be changed by pressing the
*
or
&
button followed by the
)
button to enter the
selection and return to the configuration menu.
If the
CYCLE5
function is not enabled the
following two options are available:
5td
Lower display shows the Timer's set time
5Et t
, to which the BA578E will time-up to,
or time-down from, depending upon the
direction of count selected in the
uP or dn
function.
oFF
Lower display disabled.
If the
CYCLE5
function is enabled the following
three options are available:
5td
Lower display shows the number of cycles
requested together with the current cycle
number.
During the configurable delay
period between cycles the display times-
down from the requested delay to zero. A
brief notification of timer status i.e.
CYCLE
or
dELAY
is shown at the start of each
period.
02 -11
Current
Number of cycles
cycle number.
requested, not
shown when cycle is
continuously repeated.
LabEL
Exactly the same as
5td
, but timer status
i.e.
CYCLE
or
dELAY
is shown periodically.
oFF
Lower display disabled.
5.5.9
Starting & stopping the Timer:
5tAr5toP
The Timer may be started and stopped by signals on
Input A and Input b, or by operation of the front panel
*
or
&
push buttons.
To check or change the control of the Timer, select
5tAr5toP
from the configuration menu and press
(
which will reveal the existing setting which can be
changed by pressing the
*
or
&
button followed
by the
)
button to enter the selection and return to
the configuration menu. The options available are
shown in the following tables.
Voltage inputs and control from front panel
Display
Start
Stop
ControL 1
A input high
b input high
ControL 2
A input low
b input low
ControL 3
A input high
A input low
ControL 4
A input low
A input high
LoCAL
&
button
*
button
Contact and open collector inputs
Display
Start
Stop
ControL 1
A open
b open
ControL 2
A closed
b closed
ControL 3
A open
A closed
ControL 4
A closed
A open
Proximity detector input
Display
Start
Stop
ControL 1
A low current
b low current
ControL 2
A high current
b high current
ControL 3
A low current
A high current
ControL 4
A high current
A low current
5.5.10 Units of display:
unit5
Defines the format of all displayed times, except the
delay time of the status output and optional control
outputs which are always shown in seconds and the
grand total which is always shown in hours and
tenths of an hour.
To check or change the units of display, select
unit5
from the configuration menu and press
(
which
will reveal the existing setting which can be changed
by pressing the
*
or
&
button followed by the
)
button to enter the selection and return to the
configuration menu.
The options available are
shown in the following tables:
Display
12 : 00 : 00
Hours, minutes & seconds
12 : 00
Hours & minutes
*
30 : 00
Minutes & seconds
30
Seconds
*
Only available when time specified in seconds for
5et t
and r5t
dela
are zero or exactly divisible by
60.
The Timer's maximum elapsed time in any format is
equivalent to 99hours, 59 minutes & 59 seconds.