Fig 4a  Installation into panel

Fig 4b Instrument wiring

4.3  EMC 

The BA578C complies with the requirements of the
European EMC Directive.  For specified immunity
all  wiring should be in screened twisted pairs.

5.  PROGRAMMING AND CALIBRATION

The BA578C is programmed and calibrated via four
front panel push-buttons.   All the functions are
contained in two easy to use menus, the
Programme Menu and the Trim Menu, which are
shown diagramatically in Figs 5A, 5B and 7. 

The Programme Menu contains all the transmitter
parameters and enables calibration to be
performed against the internal transmitter refer-
ences.  

The Trim Menu enables the transmitter display and
the 4/20mA output current to be calibrated against
an external standard, such as a voltage source or
temperature calibrator. This is the preferred
method of calibration.

A complete loop may be calibrated using this menu
to minimise errors resulting from primary element
and load inaccuracies.

Each function in the Programme Menu is summa-
rised in section 5.1 and includes a cross reference
to more detailed information in following sections.
Although this simple menu driven system enables
most adjustments to be made without repeated
reference to this manual, we recommend that the
summary of the Programme Menu, calibration
procedure using the Trim Menu and the calibration
example in sections 5.1,  6.1 and 7 are read prior
to changing function or calibrating the transmitter.
Figs 5A, 5B and 7 show the structure of the menus.

Details of the Trim Menu are contained in section 6
which also describes periodic calibration.

When the transmitter is fitted with alarms additional
functions are added to the programme menu.
These are described in section 10 of this manual.

Throughout this manual push-buttons are shown in
italics e.g.

 P 

or

 Up

 push-button, and legends

displayed by the transmitter are shown within
inverted commas e.g. 'CAL' and ' ALr2'.

Access to the Programme Menu is obtained by
operating the 

P

 and 

E

 push-buttons simultaneously.

If the transmitter is not protected by a security
code the first parameter 'InPut' will be displayed.  If
the transmitter is protected by a security code,  
'COdE' will be displayed first.  Pressing 

P

 again will

enable the security code to be entered digit by digit
using the 

Up

 and 

Down

 buttons to change the flash-

ing digit, and the 

P

 push-button to move to the next

digit.   If the correct code is entered pressing 

E

 will

cause the first parameter 'InPut' to be displayed.   
If an incorrect code is entered, or no button is
pressed for ten seconds, the transmitter will
automatically return to the operating mode. 

When the transmitter is in the Programme Menu the
4/20mA output current will remain locked at the
value prior to starting programming, and it will
therefore not respond to any input change.
However, calibration of the 4/20mA output via the
'CAL' function, or re-calibration of the 4/20mA
references via the 'Cond'  function will change the
output current.

Once within the Programme Menu the required
parameter can be reached by scrolling through the
functions using the 

Up 

and 

Down

 push-buttons as

shown in Figs 5A and 5B.  When returning to the
display mode following changes to any parameters,
the transmitter will display four

      6

Содержание BA578C

Страница 1: ...Issue 4 26th September 2008 BA578C panel mounting indicating temperature transmitter issue 4...

Страница 2: ...eferences 5 8 1 Conditioning internal references 5 8 2 Voltage input reference 5 8 3 3 wire RTD reference 5 8 4 4 wire RTD reference 5 8 5 Output current reference 6 Trim Menu 6 1 Calibration procedur...

Страница 3: ...ions of Section 5 you will find information on setting up for Section 6 3 Themocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 5 8 explains ho...

Страница 4: ...the 4 20mA output current The transmitter and the optional alarms are powered from the 4 20mA current loop but the optional display backlight requires a separate supply Each time power is applied to...

Страница 5: ...sed in a robust aluminium enclosure with a polyester front panel and Noryl bezel The front panel provides IP65 protection and a gasket seals the joint between the instrument and the panel The transmit...

Страница 6: ...are contained in section 6 which also describes periodic calibration When the transmitter is fitted with alarms additional functions are added to the programme menu These are described in section 10...

Страница 7: ...value Each of the functions in the Programme Menu is described in the following summary with a cross reference to more detailed information Figs 5A and 5B illustrate the location of each function wit...

Страница 8: ...8...

Страница 9: ...9...

Страница 10: ...st be entered to gain access to the programme and the trim menus Default code 0000 disables the security function and allows unrestricted access to all functions in the programme and trim menus See se...

Страница 11: ...to the sub menu 5 3 5 Input open circuit drive burn If the thermocouple fails and becomes open circuit the transmitter can be conditioned to drive the display and the 4 20mA output current up or down...

Страница 12: ...xt digit When the least significant digit has been adjusted press E to return to the dISP prompt 5 5 3 High input display calibration In HI This function defines the higher voltage input and the corre...

Страница 13: ...ned to the display mode If the security code is lost access to the Programme and Trim Menus can be obtained by putting the internal security link in the override position see Fig 6 The security code c...

Страница 14: ...mitters may be calibrated in a workshop Select 3rtd from the Cond sub menu and press P The transmitter will display scrolling decimal points while the reference is being updated followed by Ent prior...

Страница 15: ...ly trimmed at the bottom of the input range To make the adjust ment connect a calibrator to the transmitter input terminals to simulate minimum input or place the primary element in a vessel at the mi...

Страница 16: ...se to full scale The current security code is 1209 The example is divided into two sections Steps 1 to 10 explain how to condition the transmitter and to calibrate the 4 20mA output using the internal...

Страница 17: ...may be calibrated by cooling and heating the thermocouple to 10 and 240o C This is the preferred method for routine calibration Step 11 Entering the trim menu Enter the trim menu by simultaneously pr...

Страница 18: ...display mode 8 MAINTENANCE 8 1 Fault finding during commissioning If the BA578C transmitter fails to function during commissioning the following procedure should be followed Symptom Cause Solution No...

Страница 19: ...any instrument which fails We recommend that suspect instruments are returned to BEKA associates or our local agent for repair 8 4 Guarantee Transmitters which fail within the guarantee period should...

Страница 20: ...with a thermally printed tag strip on the rear panel with any legend containing up to 35 alphanumeric characters This strip is not visible from the front of the instrument after installation 10 ALARM...

Страница 21: ...alarm parameters See section 10 3 1 SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator display equals the setpoint The setpoint can also be adjusted directly fro...

Страница 22: ...22 Fig 11 Programme structure for optional alarms...

Страница 23: ...ut status select no nc from the alarm sub menu and press P to reveal the current setting The function may be changed by pressing the Up or Down buttons followed by the E button to return the no nc pro...

Страница 24: ...AcSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with thi...

Страница 25: ...installed in a poorly illuminated area The backlight is segregated from the measuring circuit and may be powered from any 18 to 30V dc supply Fig 13 Backlight power supply The brilliance of the displ...

Отзывы: